beautypg.com

Measurement interval, integration time, and filter, Measurement synchronization, App index – Yokogawa Standalone MW100 User Manual

Page 51

background image

1-37

IM MW100-01E

Explanation of Functions

1

2

3

4

5

App

Index

Resistance Temperature Detector (2 mA, cont.)

Measurement Range

Notation

Rated Measurement Range

Pt100 (high noise resistance)

Pt100-2R

–200.0 to 250.0°C

JPt100 (high noise resistance)

JPt100-2R

–200.0 to 250.0°C

Cu100 GOST

Cu100G

–200.0 to 200.0°C

Cu50 GOST

Cu50G

–200.0 to 200.0°C

Cu10 GOST

Cu10G

–200.0 to 200.0°C

DI

Measurement Range

Notation

Rated Measurement Range

LEVEL

LEVEL

Vth=2.4V

Contact input

CONTACT

100 Ω or less, ON, 10 kΩ or less, OFF

Measurement Interval, Integration Time, and Filter

You can select from the following measurement intervals for this module.
10 ms, 50 ms, 100 ms, 200 ms, 500 ms, 1 s, 2 s, 5 s, 10 s, 20 s, 30 s, 60 s
The integral time and types of filters applied vary depending on the measurement
interval.

For information on filters, see section 2.9, “Measures Against Noise on the MW100 Data

Acquisition Unit.”

Measurement Synchronization

Measurement is synchronized on each channel.

1.4 Functions of the 4-CH, High-Speed Universal Input Module