Yokogawa Standalone MW100 User Manual
Page 150
3-28
IM MW100-01E
Setting the Burnout
1.
Select the direction in which the measured value is set off the range when a
burnout detection occurs from the
Burnout list.
2.
Click the
Apply button. The setting changes take effect.
For a description of the burnout detection behavior, see “Burnout” in section 1.3.
Reference Junction Compensation
1.
Select the type of reference junction compensation in the
Type box under RJC.
2.
Enter a reference junction compensation voltage in the
Voltage[uV] box. Set
when reference junction compensation is set to External.
3.
Click the
Apply button. The setting changes take effect.
For the setting range of the RJC, see “RJC” in section 5.2.
Chattering Filter Settings
1.
In the
Chattering Filter list, turn ON the channels on which to apply the chattering
filter.
2.
Click the
Apply button. This enables the settings changes.
For information on the chattering filter, see “Filter” in section 1.9.
Setting Up and Executing Strain Input Initial Balancing
If the measurement channel is strain input, you can enter settings for executing initial
balancing. This setting is allowed even if the measurement channel is something other
than strain input, but has no effect in that case.
1.
From the top screen, click
Channel Settings > Strain Input Setting.
2.
Select the channel group you wish to set from the
Channel List list.
3.
Turn
On the channel on which you wish to perform initial balancing in the Initial
Balancing list.
4.
Click the
Apply button to finalize.
5.
Execute the
Initial Balancing item under Other Settings in the system settings.
For execution of initial balancing, see processing and operation under “Other Settings” in
section 3.3.
For a description of initial balancing, see “Initial Balancing (Unbalance Adjustment)” in
section 1.8.
3.5 Setting Measurement Conditions (Measurement Channel Settings)