5-36
IM MW100-01E
Pt100
*1
JPt100
*1
Pt100 (high res.)
JPt100 (high res.)
Ni100 SAMA
*2
Ni100 DIN
*2
Ni120
*3
Pt100 (high noise resistance)
JPt100 (high noise resistance)
Pt100 GOST
Pt100
*1
JPt100
*1
Pt100 (high res.)
JPt100 (high res.)
Pt50
*1
Cu10 GE
*4
Cu10 L&N
*4
Cu10 WEED
*4
Cu10 BAILEY
*4
J263B
Cu10 at 20°C
alpha=0.00392
Cu10 at 20°C
alpha=0.00393
Cu25 at 0°C
alpha=0.00425
Cu53 at 0°C
alpha=
0.00426035
Cu100 at 0°C
alpha=0.00425
Pt25
(JPt100/4)
Cu10 GE
(high resolution)
Cu10 L&N
(high resolution)
Cu10 WEED
(high resolution)
Cu10 BAILEY
(high resolution)
Pt100 (high noise resistance)
JPt100 (high noise resistance)
Cu100 GOST
Cu50 GOST
Cu10 GOST
Level
Contact input
–200.0 to 600.0°C
–200.0 to 550.0°C
–140.00 to 150.00°C
–140.00 to 150.00°C
–200.0 to 250.0°C
–60.0 to 180.0°C
–70.0 to 200.0°C
–200.0 to 600.0°C
–200.0 to 550.0°C
–200.0 to 600.0°C
–200.0 to 600.0°C
–200.0 to 550.0°C
–140.00 to 150.00°C
–140.00 to 150.00°C
–200.0 to 550.0°C
–200.0 to 300.0°C
–200.0 to 300.0°C
–200.0 to 300.0°C
–200.0 to 300.0°C
0.0 to 300.0K
–200.0 to 300.0°C
–200.0 to 300.0°C
–200.0 to 300.0°C
–50.0 to 150.0°C
–50.0 to 150.0°C
–200.0 to 550.0°C
–200.0 to 300.0°C
–200.0 to 300.0°C
–200.0 to 300.0°C
–200.0 to 300.0°C
–200.0 to 250.0°C
–200.0 to 250.0°C
–200.0 to 200.0°C
–200.0 to 200.0°C
–200.0 to 200.0°C
Vth = 2.4 V
±(0.05% of rdg + 0.3°C)
±(0.05% of rdg + 0.3°C)
±(0.05% of rdg + 0.3°C)
±(0.05% of rdg + 0.3°C)
±(0.05% of rdg + 0.3°C)
±(0.05% of rdg + 0.3°C)
±(0.05% of rdg + 0.3°C)
±(0.05% of rdg + 0.3°C)
±(0.1% of rdg + 0.7°C)
±(0.05% of rdg + 0.3K)
±(0.1% of rdg + 0.7°C)
±(0.1% of rdg + 0.5°C)
±(0.05% of rdg + 0.3°C)
±(0.1% of rdg + 0.5°C)
±(0.1% of rdg + 0.7°C)
±(0.05% of rdg + 0.3°C)
±(0.05% of rdg + 0.3°C)
±(0.05% of rdg + 0.3°C)
±(0.1% of rdg + 0.7°C)
Threshold level accuracy: ±0.1 V
ON for 100 Ω or less, OFF for 10 kΩ or more
*5
±(0.1% of rdg + 1.5°C)
±(0.1% of rdg + 1.5°C)
±(0.1% of rdg + 1.5°C)
±(0.1% of rdg + 2.5°C)
±(0.05% of rdg + 0.3°C)
±(0.1% of rdg + 1.5°C)
±(0.1% of rdg + 1.5°C)
±(0.1% of rdg + 1.5°C)
±(0.2% of rdg + 2.5°C)
±(0.1% of rdg + 1.5K)
±(0.2% of rdg + 2.5°C)
±(0.2% of rdg + 2°C)
±(0.1% of rdg + 1.5°C)
±(0.2% of rdg + 2°C)
±(0.2% of rdg + 2.5°C)
±(0.1% of rdg + 1.5°C)
±(0.1% of rdg + 1.5°C)
±(0.1% of rdg + 1.5°C)
±(0.2% of rdg + 0.5°C)
Input
Measurement Accuracy
Integration Time: 16.67 ms
or More
Rated
Measurement
Range
Measurement Accuracy
Integration Time: 1.67 ms
Measurement
Range
Type
*1 Pt50: JIS C 1604-1989, JIS C 1606-1989/Pt100: JIS C 1604-1997, IEC 751, DIN IEC 751/JPt100: JIS C 1604-1989, JIS C 1606-1989
*2 SAMA/DIN
*3 McGRAW EDISON COMPANY
*4 Guaranteed accuracy range Cu10 GE: –84.4 to 170.0°C/Cu10 L&N: –75.0 to 150.0°C/Cu10 WEED: –20.0 to 250.0°C/
Cu10 BAILEY: –20.0 to 250.0°C
*5 Measured using a measurement current of approximately 10μA at 200 mV range. Threshold level is approximately 0.1 V.
Highest
Resolution
(1 digit)
0.1°C
0.01°C
0.1°C
0.1°C
0.1°C
0.1°C
0.01°C
0.1°C
0.1K
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
RTD
(Measurement
current: 2 mA)
RTD
(Measurement
current: 1 mA)
DI
Measurement interval, integration time, and filter:
Measurement
Interval
10 ms
1.67 ms
*1
16.67 ms
20 ms
Auto
*2
Integration
Time
Filter
Rejected Noise and Notes
50 ms
Rectangular
100 ms
200 ms
500 ms
1 s
2, 5,10, 20, 30, 60 s
36.67 ms
100 ms
200 ms
Trapezoidal
Rectangular
Cos
600 Hz and its integer multiples
60 Hz and its integer multiples
50 Hz and its integer multiples
Automatically detects the power supply frequency and set 16.67 or 20 ms
50 Hz or 60 Hz and their integer multiples
10 Hz and its integer multiples
Fc = 5-Hz low-pass filter
*1 When the measurement interval is 10 ms, measured values may fluctuate since power supply frequency
noise is not rejected. In such cases, set the measurement interval to 50 ms or more.
*2 For DC power, set to 20 ms.
Reference junction compensation:
Switch external/internal by channel, includes remote RJC
function
5.4 4-CH, High-Speed Universal Input Module (MX110-UNV-H04) Specifications