Event action function, Event action function -19, App index event action function – Yokogawa Standalone MW100 User Manual
Page 33
1-19
IM MW100-01E
Explanation of Functions
1
2
3
4
5
App
Index
Event Action Function
The event action function is used to execute an action such as starting or stopping the
recording by detecting an event such as an alarm occurrence or digital input.
By linking the Event function and Action function, you can control the operations of the
main unit.
Event Types
The following types of events are available. Some items may not be available depending
on the options installed.
Event Type
Notation
Start Specification
Digital input
DI
Channel number
Alarm occurrence
Alarm
Alarm on specified channel
Alarm Channel
Channel number, alarm level number
Recording start
Memory
Relay action
Relay
Relay number
Timer event occurrence
Timer
Timer number
Match time event occurrence
Match Time
Match time number
User function key
User Key
Keys number
The following Actions are available. The items that can be set differ according to the
events and event detection method.
Action
Notation
Detection Method
Edge
Level
Recording start
*1
Memory Start
Recording stop
*1
Memory Stop
Save recorded data in divisions
*1
Memory Save
Save thinning recording in
Memory Save(T)
divisions
*1
Computation start
MATH Start
Computation stop
MATH Stop
Clear computation
MATH Clear
Reset computation
MATH Reset
Reset MATH on specified
MATH Reset Gr.1
MATH group number
MATH Reset Gr.2
(Gr.1-7)
MATH Reset Gr.3
MATH Reset Gr.4
MATH Reset Gr.5
MATH Reset Gr.6
MATH Reset Gr.6
Trigger occurrence on
Trigger1
specified number
Trigger2
Trigger3
Alarm ACK
Alarm ACK
Flag
Flag
Reset timer of specified
Timer 1 Reset
number (1-6)
Timer 2 Reset
Timer 3 Reset
Timer 4 Reset
Timer 5 Reset
Timer 6 Reset
1.3 Functions of the Main Module