beautypg.com

Wiring with the analog output module, Wiring with the pwm output module, Caution – Yokogawa Standalone MW100 User Manual

Page 106

background image

2-18

IM MW100-01E

Wiring with the Analog Output Module

External power supply

Voltage

V+

Load

+ 24 V

power supply

(when using current output)

Direction of

current

Vext

Current

I+

Load

CAUTION

Two power supply terminals are connected internally. Therefore, do not connect
a separate external power supply to them. Fire can result.

Main Output Specifications

Terminal type:

Clamp, attached and removed in units of 4 channels

Load impedance:

Voltage 5 kΩ or more
Current 600 Ω or less.

Applicable wire size:

0.08 to 2.5 mm

2

(AWG28 to 12)

Wiring with the PWM Output Module

External power supply

Pulse width output

V+

Load

+

4 to 28 V

power supply

CAUTION

Two power supply terminals are connected internally. Therefore, do not connect
a separate external power supply to them. Fire can result.

Main Output Specifications

Output capacity: 1A/ch max, however, 4 A or less total for all modules

*1, *2

Terminal type: Clamp, attached and removed in units of 4 channels
Applicable wire size: 0.08 to 2.5 mm

2

(AWG28 to 12)

*1

A 1A current limit circuit is built in to the output circuit. Once the current limit circuit is ON,
the circuit continues to operate unless the external power supply is turned OFF.

*2 This module has a built-in fuse. The built-in fuse protects against fires or abnormal

emissions of heat due to load short-circuiting or other abnormalities.

2.4 Connecting Signal Wires