beautypg.com

Chapter 4 troubleshooting and maintenance, Errors upon startup, System errors – Yokogawa Standalone MW100 User Manual

Page 193: Module errors, App index

background image

4-1

IM MW100-01E

Troubleshooting and Maintenance

1

2

3

4

5

App

Index

Chapter 4

Troubleshooting and Maintenance

4.1 Error Display on the 7-Segment LED and

Corrective Actions

The main module has a two-digit 7-segment LED. The 7-segment LED displays the
system status. This section describes the displays on the 7-segment LED when errors
occur on the system and their corrective actions. For information about normal displays
other than for errors, see section 1.3, “Functions of the Main Module.”
If servicing is necessary, or if the instrument is not operating correctly after performing
the corrective actions below, contact your nearest YOKOGAWA dealer.

Errors upon Startup

The left and right digits of the 7-segment LED display “b” and an error code, respectively.
The LED illuminates.

Display

Probable Cause

Corrective Action

Ref. section

b* (where *

The dip switch settings Turn OFF the power, remove the CF card, turn ON all dip

1.3

is any character are not correct.

switches, and power up again. If the situation does not change

other than F).

servicing is required.

bF

The dip switch settings Powering up in setup reset mode. Turn OFF the power, turn ON 1.3

are not correct.

all dip switches, and power up again. Since all settings such as

the IP address are initialized, reconfiguration is necessary.

System Errors

The left and right digits of the 7-segment LED display “F” and an error code, respectively.
The LED illuminates.

Display

Possible Problem

Corrective Action

Ref. section

F0

System ROM error.

Servicing required.

-

F1

SRAM error

Servicing required.

-

F2

EEPROM error

Servicing required.

-

F3

Error in the internal battery

Servicing required.

-

of the main module.

However, this error is also displayed immediately after the

battery is replaced. If this happens, power-cycle the MW100.

F4

Ethernet controller error

Servicing required.

-

F6

Web file load error

Servicing required.

-

FF

Error in writing unit information Servicing required.

-

Module Errors

The left and right digits of the 7-segment LED display are U and an error code,
respectively. The LED illuminates.
In the case of module errors, the error number and the corresponding module number
are displayed alternately as shown in the figure below.

Error number

Module number

Display

Possible Problem

Corrective Action

Ref. section

U0

Range information error.

Servicing required.

-

U1

Calibration value error.

Check the module’s installation status, then recalibrate the

-

module. If the error occurs even after recalibrating, servicing

is required.

U2

Calibration reference voltage Check whether the correct calibration reference voltage is

-

value is not correct.

being applied or whether the channel to which the voltage is

(during calibration)

applied is correct.

U3

Error in writing the calibration Servicing required.

-

value.

U4

The installed module cannot Replace the module with one that can be used.

-

be used.