beautypg.com

Yokogawa Standalone MW100 User Manual

Page 71

background image

1-57

IM MW100-01E

Explanation of Functions

1

2

3

4

5

App

Index

Output Operation during an Abnormality and after Recovery from the Abnormality

Output Operation during an Abnormality (by Module)

Abnormal Module Display Status

Output Operation

Main module bc

*1

System errors

Operation when power is turned ON

bF

Dip switches

F0

ROM error

F1

SRAM error

F2

EEPROM error

F3

Battery error

F4

Ethernet error

Output modules U0

Range information error Operation when power is turned ON or

U1

Calibration value error

when output value uncertain

U2

Error during calibration Internal communication error occurred,

resulting in an error recovery event. If

the error recovery time is 10 s or more,

output is performed per the operation for

U3

Error in writing the

error occurrence, and then output is

calibration value.

executed per the operation for power ON.

U4

Unusable modules

Operation when power is turned ON or

when output value uncertain

Input modules U0

Range information error Operation when errors occur (transmission

U1

Calibration value error

between units output only, since the

U4

Unusable modules

transmission source input channel is

illegal

*2

)

*1 The number corresponding to the error is shown in the c.
*2 Illegal occurs when a module is removed, when a module recognition fails, or when a module

malfunctions.

1.13 Operation of the 8-CH Medium-Speed Analog Output Module and the 8-CH Medium Speed PWM Output

Module