Communication errors, Settings errors, Communication errors -2 settings errors -2 – Yokogawa Standalone MW100 User Manual
Page 194
4-2
IM MW100-01E
Communication Errors
The left and right digits of the 7-segment LED display “C” and an error code, respectively.
The LED blinks.
Display
Possible Problem
Corrective Action
Ref. section
C0
DHCP address
Check network connections. Use a Fixed IP address
2.6, 3.2 *
acquisition error
Check with your network administrator whether your environment
supports acquisition of addresses by DHCP.
C1
DNS name error
Check network connections. Check with your network manager
2.6 *
to determine whether your environment supports host name
registration.
* See the MW100 Viewer Software User’s Manual (IM MW180-01E).
Settings Errors
The code is divided into two parts which are displayed alternately on the 7-segment LED;
in the first part, the letter E appears in the left digit with the hundreds digit of the error
code to the right, and the second part consists of the last two digits of the error code.
Display
Possible Problem
Corrective Action
E001
Invalid function parameter.
Enter the correct parameter.
E002
Value exceeds the setting range.
Set a value within the allowable range.
E003
Incorrect real number format.
Use the correct real number format.
E004
Real number value exceeds the setting range.
Set a real number within the allowable range.
E005
Incorrect character string.
Set an allowable character string.
E006
Character string too long.
Set a character string within the allowable length.
E007
Incorrect display color format.
Specify a display color using the correct format.
E008
Incorrect date format.
Enter the date using the correct format.
E009
Data value exceeds the setting range.
Set a date within the allowable range.
E010
Incorrect time format.
Enter the time using the correct format.
E011
Time value exceeds the setting range.
Set a time within the allowable range.
E012
Incorrect time zone format.
Specify a time zone using the correct format.
E013
Time zone value exceeds the setting range.
Set a time zone within the allowable range.
E014
Incorrect IP address format.
Enter an IP address using the correct format.
E020
Invalid channel number.
Enter the correct channel number.
E021
Invalid sequence of first and last channel.
Set a value for the last channel that is greater or equal to than
the first channel.
E022
Invalid alarm number.
Enter the correct alarm number.
E023
Invalid relay number.
Enter a correct relay number.
E024
Invalid sequence of first and last relay.
Set a value for the last relay that is greater or equal to than the
first relay.
E025
Invalid MATH group number.
Enter a correct MATH group number.
E026
Invalid box number.
Enter the correct box number.
E027
Invalid timer number.
Enter the correct timer number.
E028
Invalid match time number.
Enter the correct match time number.
E029
Invalid measurement group number.
Enter a correct measurement group number.
E030
Invalid module number.
Enter a correct module number.
E031
Invalid start and end time of DST.
Enter a correct start and end time.
E032
Invalid display group number.
Enter a correct display group number.
E033
Invalid tripline number.
Enter a correct tripline number.
E034
Invalid message number.
Enter a correct message number.
E035
Invalid user number.
Enter a correct user number.
E036
Invalid server type.
Enter a correct destination type.
E037
Invalid e-mail contents.
Enter a correct send destination.
E038
Invalid server number.
Enter a correct server number.
E039
Invalid command number.
Enter a correct command number.
4.1 Error Display on the 7-Segment LED and Corrective Actions