1-44

IM MW100-01E

Resistance Temperature Detector (1 mA, cont.)

Measurement Range

Notation

Rated Measurement Range

J263B

J263B

0.0 to 300.0K

Cu10 at 20°C

Cu10a392

–200.0 to 300.0°C

alpha=0.00392
Cu10 at 20°C

Cu10a393

–200.0 to 300.0°C

alpha=0.00393
Cu25 at 0°C

Cu25

–200.0 to 300.0°C

alpha=0.00425
Cu53 at 0°C

Cu53

–50.0 to 150.0°C

alpha=0.00426035
Cu100 at 0°C

Cu100

–50.0 to 150.0°C

alpha=0.00425
Pt25 (JPt100 × 1/4)

Pt25

–200.0 to 550.0°C

Cu10 GE (high resolution)

Cu10GEH

–200.0 to 300.0°C

Cu10 L&N (high resolution)

Cu10LNH

–200.0 to 300.0°C

Cu10 WEED (high resolution)

Cu10WEEDH

–200.0 to 300.0°C

Cu10 BAILEY (high resolution)

Cu10BAILEYH

–200.0 to 300.0°C

Pt100 GOST

Pt100G

–200.0 to 600.0°C

Cu100 GOST

Cu100G

–200.0 to 200.0°C

Cu50 GOST

Cu50G

–200.0 to 200.0°C

Cu10 GOST

Cu10G

–200.0 to 200.0°C

Resistance Temperature Detector (0.25 mA)

Measurement Range

Notation

Rated Measurement Range

Pt500

Pt500

–200.0 to 600.0°C

Pt1000

Pt1000

–200.0 to 600.0°C

Resistance

Measurement Range

Notation

Rated Measurement Range

20 Ω (measured current 1 mA)

20 ohm

0.000 to 20.000 Ω

200 Ω (measured current 1 mA)

200 ohm

0.00 to 200.00 Ω

2 kΩ (measured current 0.25 mA)

2000 ohm

0.0 to 2000.0 Ω

DI

Measurement Range

Notation

Rated Measurement Range

LEVEL

LEVEL

Vth=2.4V

Contact input

CONTACT

1 kΩ or less, ON, 100 kΩ or less, OFF

(shunt capacitance: 0.01 µF or less)

Measurement Interval, Integration Time, and Filter

You can select from the following measurement intervals for this module.
100 ms, 200 ms, 500 ms, 1 s, 2 s, 5 s, 10 s, 20 s, 30 s, 60 s
The integral time and types of filters applied vary depending on the measurement
interval.

For information on filters, see section 2.9, “Measures Against Noise on the MW100 Data

Acquisition Unit.”

Measurement Synchronization

Since measurement is sequential, measurement on each channel is not synchronized.

1.7 Functions of the 6-CH, Medium-Speed Four-Wire RTD Resistance Input Module