Connecting with serial communication (optional), Connecting with serial communication (optional) -8 – Yokogawa Standalone MW100 User Manual
Page 130
3-8
IM MW100-01E
Connecting with Serial Communication (Optional)
You can enter settings using a browser, or with communication commands. The following
explains setting entry using a browser.
For information about communication commands, see the Communication Command
Manual
(IM MW100-17E).
1.
From the
Top screen, click Communication Setting > Serial Communication
Setting.
Receiver Settings
2.
In the
Function list, select Normal for the MW100-specific protocol, Modbus
Master for the Modbus protocol master, or Modbus Slave for the Modbus
protocol slave.
3.
Enter an address number in the
Address box. Select the address in the range of
1 to 32 for the MW100-specific protocol and 1 to 247 for the Modbus slave.
Data Transfer Settings
4.
Select a baud rate in the
Baud Rate list.
5.
Select a parity check method in the
Parity Bit list.
6.
Select a number of bits from the
Stop Bit list.
7.
Select a communication data length from the
Data Length list. Be sure to select 8
bits if you are outputting the data in binary format.
8.
Select a handshaking method in the
Handshake list. This setting is valid only for
the RS-232 interface.
For a description of the setup parameters of data transmission, see “Communication” in
section 5.2.
9.
Click the
Apply button. The setting changes take effect.
3.2 Communication Settings