beautypg.com

Appendix 4 e-mail format, Alarm notification e-mail format – Yokogawa Standalone MW100 User Manual

Page 285

background image

App-11

IM MW100-01E

Appendix

1

2

3

4

5

App

Index

Appendix 4 E-Mail Format

In the explanations that follow, CRLF means “carriage return/line feed.”
A user-defined character string can be attached to the subject of each mail.

Alarm Notification E-mail Format

• Subject

Subject: [Alarm Summary]

• Syntax

CRLF
Alarm_SummaryCRLF
DATE_yy/mo/ddCRLF
TIME_hh:mi:ssCRLF
CRLF
CRLF
cc____lq_aaaCRLF
∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙
mmmm_lq_aaaCRLF
∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙
CRLF
CRLF
ccc*ddddddd_[uuuuuu]CRLF
∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙
mmmm*eeeeeeeee_[uuuuuu]CRLF
∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙
CRLF
ENDCRLF
CRLF

yy Year (00 to 99)
mo Month (01 to 12)
dd Day (01 to 31)
hh Hour (00 to 23)
mi Minute (00 to 59)
ss Seconds (00 to 59)
* Tab
ccc Measurement ch no. (001 to 060, SKIP channels not output)
mmmm MATH ch no. (A001 to A300, OFF channels not output)
l Alarm level (1 to 4)
q Alarm type (H, L, h, l, R, r, T, t)

H (upper limit alarm), L (lower limit alarm), h (differential upper limit
alarm),

l (differential lower limit alarm), R (upper limit on rate-of-

change alarm),

r (lower limit on rate-of-change alarm), T (delay

upper limit alarm),

t (delay lower limit alarm)

aaa Alarm status (off, on)
ddddddd Measured data (measurement channel, includes decimal point and

minus sign, all space filled in to the left when 6 characters or fewer)

eeeeeeeee Computed data (MATH channel, includes decimal point and minus

sign, all space filled in to the left when 8 characters or fewer)