Appendix 4 e-mail format, Alarm notification e-mail format – Yokogawa Standalone MW100 User Manual
Page 285
App-11
IM MW100-01E
Appendix
1
2
3
4
5
App
Index
Appendix 4 E-Mail Format
In the explanations that follow, CRLF means “carriage return/line feed.”
A user-defined character string can be attached to the subject of each mail.
Alarm Notification E-mail Format
• Subject
Subject: [Alarm Summary]
• Syntax
CRLF
Alarm_SummaryCRLF
DATE_yy/mo/ddCRLF
TIME_hh:mi:ssCRLF
CRLF
cc____lq_aaaCRLF
∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙
mmmm_lq_aaaCRLF
∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙
CRLF
ccc*ddddddd_[uuuuuu]CRLF
∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙
mmmm*eeeeeeeee_[uuuuuu]CRLF
∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙
CRLF
ENDCRLF
CRLF
yy Year (00 to 99)
mo Month (01 to 12)
dd Day (01 to 31)
hh Hour (00 to 23)
mi Minute (00 to 59)
ss Seconds (00 to 59)
* Tab
ccc Measurement ch no. (001 to 060, SKIP channels not output)
mmmm MATH ch no. (A001 to A300, OFF channels not output)
l Alarm level (1 to 4)
q Alarm type (H, L, h, l, R, r, T, t)
H (upper limit alarm), L (lower limit alarm), h (differential upper limit
alarm),
l (differential lower limit alarm), R (upper limit on rate-of-
change alarm),
r (lower limit on rate-of-change alarm), T (delay
upper limit alarm),
t (delay lower limit alarm)
aaa Alarm status (off, on)
ddddddd Measured data (measurement channel, includes decimal point and
minus sign, all space filled in to the left when 6 characters or fewer)
eeeeeeeee Computed data (MATH channel, includes decimal point and minus
sign, all space filled in to the left when 8 characters or fewer)