Yokogawa Standalone MW100 User Manual
Page 196
4-4
IM MW100-01E
Display
Possible Problem
Corrective Action
E112
Invalid relay number for relay event.
Set the channel number for the DO module.
E113
Invalid action type.
Enter a correct action type.
E114
Invalid combination of edge and level detection
Set the edge and level detection types to something different.
actions.
E115
Invalid combination of level detection actions.
Set events of different types to different actions in level
detection.
E116
Invalid flag number.
Enter a correct flag number.
E120
Invalid measurement group number.
Set the measurement interval so that meas. gr 1 ≤ meas. gr 2
≤ meas. gr 3. The maximum allowable ch for 10 ms
measurement is 10, and for 50 ms, 30.
E121
Invalid measurement group number for MATH
Set MATH interval to a measurement group of 100 ms or
interval.
longer.
E130
Size of data file for measurement group 1
Set the number of saved channels, recording interval, and
exceeds the upper limit.
recording data length so that the data file of measurement
group 1 does not exceed 10 MB.
E131
Size of data file for measurement group 2
Set the number of saved channels, recording interval, and
exceeds the upper limit.
recording data length so that the data file of measurement
group 2 does not exceed 10 MB.
E132
Size of data file for measurement group 3
Set the number of saved channels, recording interval, and
exceeds the upper limit.
recording data length so that the data file of measurement
group 3 does not exceed 10 MB.
E133
Size of MATH data file exceeds the upper limit.
Set the number of saved channels, recording interval, and
recording data length so that the MATH data file does not
exceed 10 MB.
E134
Size of thinned data file exceeds the upper limit.
Set the number of saved channels, recording interval, and
recording data length so that the thinned data file does not
exceed 10 MB.
E135
Cannot set smaller value for thinning recording
Set a value for the thinning recording interval higher than
interval than measuring or MATH interval.
the measurement and MATH interval.
E136
Invalid combination of thinning recording,
Set a value for the thinning recording interval that is a common
measuring and MATH interval.
multiple of the measurement and MATH intervals.
E137
Combination of thinning recording interval and
Set the thinning recording data length to an integer multiple
thinning recording data length incorrect.
of the thinning recording interval.
E138
Cannot set recording operation for measurement Set the measurement interval of the measurement group
group with no measuring interval.
number to something other than OFF.
E139
Invalid recording interval.
Set a recording interval which can be set to the measurement
interval of the measurement group.
E140
Upper and lower limits of the display zone cannot Set the upper and lower limits of display zone to a different
be equal.
value.
E141
Cannot set smaller value than lower limit of
Set a larger value for the upper limit than that of the lower limit.
display zone for upper limit.
E142
Width of display zone must be 5% of that of the
Set the upper and lower limits so that the difference between
entire display or more.
them is 5% or more.
E145
Incorrect display group format.
Enter a display group of the correct format.
E150
IP address must belong to class A, B, or C.
Set an IP address belonging to class A, B, or C.
E151
Net or host part of IP address is all 0’s or 1’s.
Set a valid combination of IP address and subnet mask.
E152
Invalid subnet mask.
Enter a setting according to your network.
E153
Invalid gateway address.
Make sure that the network part of the IP address and default
gateway match.
E160
Incorrect alarm e-mail channel format.
Specify a channel using the correct format.
E165
Invalid channel number for Modbus command.
Enter a correct channel.
E166
Invalid combination of start and end channel for
Set the first and last channel to the same type.
Modbus command.
E167
Invalid sequence of start and end channel for
Set the last channel equal or greater than the first channel.
Modbus command.
E168
Too many channels for command number.
Set a valid number of channels for the data type.
E170
Invalid channel number for report.
Set the channel included on the input module.
4.1 Error Display on the 7-Segment LED and Corrective Actions