beautypg.com

Output types, Output update interval, Relay excitation state / hold operation – Yokogawa Standalone MW100 User Manual

Page 73: App index

background image

1-59

IM MW100-01E

Explanation of Functions

1

2

3

4

5

App

Index

1.14 Functions of the 10-CH, Medium-Speed Digital

Output Module

This module has ten contact signal outputs that are based on alarm output settings and
output settings from the PC.

Output terminal (clamp terminal)

Terminal cover

Output Types

The following types (output factors) are available.

Type

Notation

Description

Alarm

Alarm

Measurement and MATH channels

Manual

Comm.Input Manual DO operation(Relay turns ON/OFF depending on the value

sent from the PC)

Media

Media

When determined that no space remains within the specified “remaining

space time

*

Fail

Fail

When an abnormality occurs on the CPU of the MW100 main module

Error

Error

When an error is detected on the MW100

(abnormal or missing module, etc.)

* Firmware version R3.03 or later

Output Update Interval

The output is updated at 100-ms intervals. It is not synchronized to the measurement
interval.

Relay Excitation State / Hold Operation

You can select whether or not to energize the output relays upon output. The excitation
status selection differs depending on the output type.

Excitation Notation

Description

Available Output Types

Status
Energize

Energize

Energize when relay output is ON

Alarm/Comm.Input/Error/Media

De-energize De-energize Not energize when relay output is ON Alarm/Comm.Input/Fail