Output types, Output method, Output range – Yokogawa Standalone MW100 User Manual
Page 66: Output update interval, Operation upon startup and errors, Output operation during calibration
1-52
IM MW100-01E
1.11 Functions of the 8-CH, Medium-Speed Analog
Output Module
The module has eight outputs for voltage or current.
An external power source (24 V) is required for current output.
For voltage output only, an external power source is not required.
Input terminal (clamp terminal)
Terminal cover
Output Types
Output Type
Notation
No output
SKIP
Analog output
AO
Output Method
Output Method
Notation
Actions
Transmission output
Trans
Outputs a voltage or current according to the
measured or computed data of the input channel
specified on the same unit. You can also produce
pattern output using the broken line input function.
Arbitrary output
Comm.Input
Outputs specified values based on values sent from
the PC.
Output Range
Output Range
Notation
Output range
Voltage
10 V
–10.000 V to 10.000 V
Current
20 mA
0.000 mA to 20.000 mA
Output Update Interval
The output is updated at 100-ms (minimum) intervals. It is not synchronized to the
measurement interval.
Operation upon Startup and Errors
See section 1.13, “Operation of the Eight-Channel Medium-Speed Analog Output Module
and the Eight-Channel Medium Speed PWM Output Module.”
Output Operation during Calibration
Calibration Condition
Output Operation
Channels being calibrated
Arbitrary output (output of calibration value)
Non-calibrated channels
Holds the output value (holds the value last output during steady
operation (see section 1.13))