5.7 6-CH, Medium-Speed Four-Wire RTD

Resistance Input Module (MX110-V4R-M06)

Specifications

Style number:

S2

Type of measurement: DC voltage, 4-wire RTD, 4-wire resistance, DI (contact, LEVEL)
Number of inputs:

6

Input method:

Floating unbalanced input, insulation between channels

A/D resolution:

16 bits (±20000/±6000/0 to 60000)

Measurement range and accuracy:

The accuracy applies to standard operating conditions:

Ambient temp: 23 ±2°C, ambient humidity: 55 ±10% RH, supply
voltage: 90 to 250 VAC, power frequency: 50/60 Hz ±1%, warm-
up time: at least 30 minutes, without adverse conditions such as
vibrations.

20 mV

60 mV

200 mV

2 V

6 V

20 V

100 V

60 mV (high res.)

6 V (high res.)

1 V

Pt100

*1

JPt100

*1

Pt100 (high res.)

JPt100 (high res.)

Ni100 SAMA

*2

Ni100 DIN

*2

Ni120

*3

Pt50

Cu10 GE

*4

Cu10 L&N

*4

Cu10 WEED

*4

Cu10 BAILEY

*4

J263B

Cu10 at 20°C

alpha=0.00392

Cu10 at 20°C

alpha=0.00393

Cu25 at 0°C

alpha=0.00425

Cu53 at 0°C

alpha=

0.00426035

Cu100 at 0°C

alpha=0.00425

Pt25

(JPt100/4)

Cu10 GE

(high resolution)

Cu10 L&N

(high resolution)

Cu10 WEED

(high resolution)

Cu10 BAILEY

(high resolution)
Pt100 GOST

Cu100 GOST

Cu50 GOST

Cu10 GOST

DC voltage

–20.000 to 20.000 mV

–60.00 to 60.00 mV

–200.00 to 200.00 mV

–2.0000 to 2.0000 V

–6.000 to 6.000 V

–20.000 to 20.000 V

–100.00 to 100.00 V

0.000 to 60.000 mV

0.0000 to 6.0000 V

–1.0000 to 1.0000 V

–200.0 to 600.0°C

–200.0 to 550.0°C

–140.00 to 150.00°C

–140.00 to 150.00°C

–200.0 to 250.0°C

–60.0 to 180.0°C

–70.0 to 200.0°C

–200.0 to 550.0°C

–200.0 to 300.0°C

–200.0 to 300.0°C

–200.0 to 300.0°C

–200.0 to 300.0°C

0.0 to 300.0K
–200.0 to 300.0°C

–200.0 to 300.0°C

–200.0 to 300.0°C

–50.0 to 150.0°C

–50.0 to 150.0°C
–200.0 to 550.0°C
–200.0 to 300.0°C

–200.0 to 300.0°C

–200.0 to 300.0°C

–200.0 to 300.0°C

–200.0 to 600.0°C

–200.0 to 200.0°C

–200.0 to 200.0°C

–200.0 to 200.0°C

±(0.05% of rdg + 0.3°C)

±(0.05% of rdg + 0.3°C)

±(0.05% of rdg + 0.3°C)

±(0.1% of rdg + 2°C)

±(0.05% of rdg + 0.3K)

±(0.1% of rdg + 2°C)

±(0.1% of rdg + 0.5°C)

±(0.05% of rdg + 0.3°C)

±(0.1% of rdg + 0.5°C)

±(0.1% of rdg + 2°C)

±(0.05% of rdg + 0.3°C)

±(0.05% of rdg + 0.3°C)

±(0.05% of rdg + 0.3°C)

±(0.1% of rdg + 2°C)

±(0.1% of rdg + 25 digits)

±(0.1% of rdg + 10 digits)

±(0.1% of rdg + 100 digits)

±(0.1% of rdg + 100 digits)

±(0.1% of rdg + 10 digits)
±(0.1% of rdg + 1.5°C)

±(0.1% of rdg + 1.5°C)

±(0.1% of rdg + 1.5°C)

±(0.2% of rdg + 5°C)

±(0.1% of rdg + 1.5K)

±(0.2% of rdg + 5°C)

±(0.2% of rdg + 2°C)

±(0.1% of rdg + 1.5°C)

±(0.2% of rdg + 2°C)

±(0.2% of rdg + 5°C)

±(0.1% of rdg + 1.5°C)

±(0.1% of rdg + 1.5°C)

±(0.1% of rdg + 1.5°C)

±(0.2% of rdg + 5°C)

Input

Measurement Accuracy

Integration Time: 16.67 ms

or More

Rated

Measurement

Range

Measurement Accuracy

Integration Time: 1.67 ms

Measurement

Range

Type

*1 Pt50: JIS C 1604-1989, JIS C 1606-1989/Pt100: JIS C 1604-1997, IEC 751, DIN IEC 751/JPt100: JIS C 1604-1989, JIS C 1606-1989

*2 SAMA/DIN

*3 McGRAW EDISON COMPANY

*4 Guaranteed accuracy range Cu10 GE: –84.4 to 170.0°C/Cu10 L&N: –75.0 to 150.0°C/Cu10 WEED: –20.0 to 250.0°C/

Cu10 BAILEY: –20.0 to 250.0°C

*5. 4-wire RTD, 4-wire resistance

Highest

Resolution

(1 digit)

1 µV

10 µV

10 µV

100 µV

1 mV

1 mV

10 mV

1 µV

100 µV

100 µV
0.1°C

0.01°C

0.1°C

0.1°C

0.1K

0.1°C

0.1°C

0.1°C

0.1°C

0.1°C

0.1°C

0.1°C

0.1°C

0.1°C

RTD

*5

(Measurement

current: 1 mA)

±(0.05% of rdg + 5 digits)

±(0.05% of rdg + 2 digits)

±(0.05% of rdg + 2 digits)

±(0.05% of rdg + 5 digits)

±(0.05% of rdg + 2 digits)

±(0.05% of rdg + 2 digits)

±(0.05% of rdg + 2 digits)

±(0.05% of rdg + 20 digits)

±(0.05% of rdg + 20 digits)

±(0.05% of rdg + 2 digits)