Example of a connection with an upstream device, Wire – Yokogawa Standalone MW100 User Manual
Page 114
2-26
IM MW100-01E
Example of a Connection with an Upstream Device
You can connect the MW100 to an upstream device with an RS-232, RS-422A, or RS485
connection port.
For RS-232, use a converter. Refer to the following table for connections to most
converter terminals. For details, see the manual that came with the converter.
RS-422A/485 Port
Converter
SDA(–)
TD(–)
SDB(+)
TD(+)
RDA(–)
RD(–)
RDB(+)
RD(+)
SG
SHIELD
FG
EARTH
4-Wire
In general, a 4-wire connection is used with upstream devices. For a 4-wire connection,
the send and receive wires must be crossed.
Termination resistance (externally attached) 120 Ω 1/2 W or more
#
1
Do not connect termination resistance from #1 to #n–1.
Main unit
RS-422A/485
terminals
#
2
#
n
(
#
n32)
Termination resistance
(built-in: with switch)
Upstream
instrument
SG
RDB( + )
RDA( – )
SDB( + )
SDA( – )
FG
SG
RD B
RD A
SD B
SD A
(SG)
(RD B)
(RD A)
(SDB)
(SDA)
FG
SG
RD B
RD A
SD B
SD A
(SG)
(RD B)
(RD A)
(SDB)
(SDA)
FG
SG
RD B
RD A
SD B
SD A
(SG)
(RD B)
(RD A)
(SDB)
(SDA)
2-Wire
On the RS-422A/485 terminal block, connect signals of the same polarity for sending and
receiving, and connect only two wires externally.
Termination resistance (externally attached) 120 Ω 1/2 W or more
#
1
Do not connect termination resistance from #1 to #n–1.
Main unit
RS-422A/485
terminals
#
2
#
n
(
#
n31)
Termination resistance
(built-in: with switch)
Upstream
instrument
SG
RDB( + )
RDA( – )
SDB( + )
SDA( – )
FG
SG
RD B
RD A
SD B
SD A
(SG)
(B)
(A)
(B)
(A)
FG
SG
RD B
RD A
SD B
SD A
(SG)
FG
SG
RD B
RD A
SD B
SD A
(SG)
(B)
(A)
2.7 Connecting the RS-422A/485 Interface (/C3 Option)