Thermocouple (cont.)

Measurement Range

Notation

Rated Measurement Range

Type-N

N

0.0 to 1300.0°C

Type-W

W

0.0 to 2315.0°C

Type-L

L

–200.0 to 900.0°C

Type-U

U

–200.0 to 400.0°C

KPvsAu7Fe

KPvsAu7Fe

0.0 to 300.0 K

PLATINEL

PLATINEL

0.0 to 1400.0°C

PR40-20

PR40-20

0.0 to 1900.0°C

NiNiMo

NiNiMo

0.0 to 1310.0°C

WRe3-25

WRe3-25

0.0 to 2400.0°C

W/WRe26

WWRe26

0.0 to 2400.0°C

Type-N (AWG14)

N14

0.0 to 1300.0°C

Type-XK GOST

XK

–200.0 to 600.0°C

DI

Measurement Range

Notation

Rated Measurement Range

LEVEL

LEVEL

Vth=2.4 V

Contact input

CONTACT

1 kΩ or less, ON, 100 kΩ or less, OFF

(shunt capacitance: 0.01 μF or less)

Measurement Interval, Integration Time, and Filter

You can select from the following measurement intervals for this module.
500 ms, 1 s, 2 s, 5 s, 10 s, 20 s, 30 s, or 60 s.
The integral time and types of filters applied vary depending on the measurement
interval.

For information on filters, see section 2.9, “Measures Against Noise on the MW100 Data

Acquisition Unit.”

Measurement Synchronization

Since measurement is sequential, measurement on each channel is not synchronized.