4.6 System Initialization

Perform this procedure to initialize the settings on the MW100. The following types of
initialization are available.

Initialization Type

Type

Level

Items Initialized

Initialization using dip switches ----

All settings

Initialization using

All

Setting other than configurated module

communication commands

information

All except Comm. Settings excluding the following items

(IP address, host name, subnet mask, default

gateway, DHCP parameters, DNS parameters,

communication timeout parameters, login

parameters, baud rate, parity bit, stop bit, data

length, handshaking, and module recognition

information)

Initialization Procedure

Using Dip Switches

1.

Turn OFF the power to the MW100.

2.

Check that the switch 5 of dip switch 1 on the main module is OFF.

1 2 3 4 5 6 7 8

ON

3.

Turn OFF the power to the MW100.

After the 7-segment LED indicates the power ON self check, bF is displayed.

4.

Check the status of step 3, then turn the power OFF.

5.

Turn switch 5 of dip switch 1 ON.

Initialization using communication commands

Using a Browser
For information about initialization using communication command, see the MW100
Communication Command Manual
(IM MW100-17E).

1.

From the top screen, click

System Settings > Module Information under the

Top item.

2.

Select the initialization level from the

Initialization Level box under System

information.

3.

Click the

Initialize button. Initialization is performed.

For a description of the operation screen for initialization, see section 3.3, “System Settings.”