Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-63
The term local set means that communication is lost between the
Central Processing Unit (CPU) and the satellite controllers. If the
CPU stops communicating, the global analog values will be gone.
This input allows you to specify a default value for the global
analog if the CPU quits communicating. You may input a fi xed
number, or you may choose to select LAST VALUE. If LAST
VALUE is chosen, the global analog will default to the value it had
when communications with the CPU were lost.
Mode
Because this is a “choice” fi eld, the list of available choices will be
displayed at the bottom of the screen:
CHOICES:
Make your selection by pressing the
once for each
choice until the desired mode type has been selected, and then press
. One of the following screens will appear, depending on
which choice you select:
Averaged List
Math Function
Sorted List
Look-Up Table
Integral
External
Sliding
Window
Average
Accumulation
CAUTION
Select the mode before entering any other data on
an Analog Global Screen. If other information is entered before
the mode is selected, there is a chance that the global analog
will not perform properly. If data has already been entered and
you want to change the mode, you must fi rst clear the screen by
using the
feature, and then exit to the Global
Analog Summary Screen before re-entering data.