Alarm summary screen – WattMaster WCC II User Manual
Page 68

Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-36
Address:
This location designates the address which is, or has been, in alarm
and has not been acknowledged. The listing for the alarm addresses
will be in sequential order from the lowest satellite number to the
highest satellite number. Twenty alarms can be viewed on one
screen. To move from the present twenty alarms to the next set
of twenty alarms, simply press
(Page Down) located
on the keypad to the right of the keyboard. To view the previous
twenty alarms, simply press
(Page Up) also located on
the keypad.
Alarm Screen Access
If you would like to view any of these alarms, you may move the
cursor (>) to the desired alarm by using the arrow keys located on
the keypad and then pressing
. This will bring you to the
summary screen of the point in alarm. At this summary screen you
may acknowledge the alarm if desired. (For further information on
acknowledging alarms, refer to the Analog Input Summary Screen
section on page 3-7.)
An alarm may be acknowledged at the Alarm Summary Screen by
using the arrow keys to move the cursor (>) to the desired alarm
and pressing
. To perform a
function, press
down and then press
, holding both keys down at the
same time and then releasing both keys. The alarm message will
automatically disappear, but the address, class, and description will
remain until you have exited the screen. When you return to the
Alarm Summary Screen, this information will be gone.
If you would like to acknowledge all of the alarms at once, press
and
simultaneously while the cursor is at the top of this
screen.
Class:
This location designates the class level (1-8) which has been
assigned to the alarm. 1 is the highest priority, and 8 is the lowest
priority.
Pending:
If the system has detected an alarm but has not reported it on the
local or remote printer, a message will show up indicating an alarm
is pending. PRT will appear when an alarm is waiting to print on
the local printer, and CAL will appear when an alarm is waiting to
call out. If the local has been disabled using the System Parameter
II Screen, the PRT message will not appear.
Description:
This location displays the description message of the address.
This information comes from the description area of the screen
corresponding to that particular address.
Alarm Message(s):
This location will display the alarm message associated with the
particular alarm. If the address was assigned two alarm messages
(a low message and a high message), the alarm which is initiated
fi rst will appear under the Alarm Message(s) section. If a second
alarm exists, it will appear after the fi rst message which is located
under the time and date location.
If you have a high and/or low alarm message and wish to see at
what time and on what day the alarm occurred, you will need to
go to the summary screen for the particular address to view this
information.
-----------------------------------------------------------------------------------------
Alarm
Summary
Time
Date
Address
Class Pending
Description Alarm Message(s) 11:54 7/21
1A1
5
TRAININ RM
Temp Too Low
1T3r
2
AHU
Motor
Chg
Filters
HOME for menu
-----------------------------------------------------------------------------------------
-
ALARM SUMMARY SCREEN