beautypg.com

Energy consumption screen – WattMaster WCC II User Manual

Page 85

background image

Section 3: Screen Descriptions

WCC II Operator’s Guide

Operator Interfaces

3-53

The ECC/WCC II system has ten Energy Consumption Screens.
The number directly under the ENERGY CONSUMPTION
SUMMARY title is the number of the screen. To change the
number, move the cursor to this fi eld, enter the number you would
like, and then press

.

Building A

The same message that is entered on the System Parameter Screen
to identify the system is automatically printed on the Energy
Consumption Screen
.

Satellite #: 1

Enter the number of the satellite controller which has the pulse
type kw meter connected to it. (Note: The pulse meter must be
connected to the analog input #1 on the satellite controller, and the
pulse switch on the front of the satellite controller must be in the
“On” position.)

Current Demand:
Consumption Since Last Reset:

The current demand and the current consumption since last reset
are automatically displayed here. To reset the consumption, with
the cursor in the home position on the screen, press

and

then

, holding both keys down at the same time for an instant

and then releasing both keys at the same time.

The following units may be selected for consumption by placing
the cursor over the units for the “Consumption since last reset,”
pressing the

until the desired units appear, and then

pressing

.

KWH = 1 KWH
DKH = 10 KWH
HKH = 100 KWH
MWH = 1,000 KWH
DMH = 10,000 KWH
HMH = 100,000 KWH
GWH = 1,000,000 KWH
DGW = 10,000,000 KWH

5428 KWH will appear as 543 DKH
5428 KWH will appear as 54 HKH etc.

The units selected will appear for the consumption since last reset
and also for the monthly consumption. The maximum value of
9999 for monthly consumption should be taken into consideration
when selecting units. The signifi cant fi gures will be adjusted as
different choices are selected. For example, if you have a present
value of 5428 KWH,and you change the units from KWH to HKH,
54 HKH will appear on the screen. If you then change back to
KWH, 5400 KWH will appear.

ENERGY CONSUMPTION SCREEN

----------------ENERGY CONSUMPTION SUMMARY----------------

1

11:29

2/23

Building A

----------Current Consumption Statistics----------

Satellite #: 1

Current Demand: 50 KW

Consumption Since Last Reset: 3500 DKH

Demand From: GAO

-----------Energy Consumption History----------

Today

Yesterday

This Month

Last Month

Consumption:

1000 KWH

1200 KWH

1200 DKH

4200 DKH

Peak Demand:

62 KW

65 KW

65 KW

72 KW

Time of Peak:

10:20

16:05

14:30 2/10

16:50 1/25

Consumption Past 12 Months in DKH Average over 12 Months 6200 DHK

JAN

5600 NOV 6600

SEP 3450 JUL 6780 MAY 5700 MAR 5600

DEC

4600 OCT 6000

AUG 8900 JUN 7700 APR 4600 FEB 5000