Tuc-vr ea driver screen – WattMaster WCC II User Manual

Page 182

background image

Section 3: Screen Descriptions

WCC II Operator’s Guide

Operator Interfaces

3-150

Analog Control by:

Specifi es the analog point address that acts as the input signal source
for this control output. This input is forced to be the temperature
sensor wired to the specifi c TUC-VR represented by this screen. A
sensor wired to another TUC-VR or a global analog value cannot
be used as the analog input for a TUC-VR. In other words, the
“Analog Control by” value for a TUC-VR is always the room
temperature sensor connected to that particular TUC-VR.

Schedule Control by: ______

The “Occupied or Unoccupied” control setpoints for the TUC-
VR are selected using the “Schedule Control by:” input on
this EA Driver Screen. When the value of this input is ON,
the TUC-VR will control according to the “On Schedule”
setpoints. When the value of this input is OFF, the TUC-
VR will control according to the “Off Schedule” setpoints.

-----------

Setpoints

---------------

On Schedule: _______

Alternate On: _______

Off Schedule: _______

Off:

_______

Selected

by:

_______

Specifi es a set of analog setpoints (4 total) for the ON and OFF
normal mode schedule, ON and OFF alternate mode schedule. The
alternate setpoints are used when the “Selected by:” binary value
is On.

The TUC-VR tries to maintain the temperature setpoint entered
here by modulating the primary air damper in the terminal unit
controller.

The heating setpoint is an “offset value” entered on the TUC-VR
Setup Screen
. That is, if 76 °F is entered as the setpoint on this EA
Driver Screen
, and 4 °F is entered as the “heating offset” on the
TUC-VR Screen, the heating setpoint will be 72 °F (76-4 = 72).

TUC-VR EA DRIVER SCREEN

-----------------------------------------------------------------------------------------

-

Satellite # 4

CONTROL OUTPUT 2

Mode: EA Driver

Description: TUC-VR

4.2

COM to H on decreasing control signal

Analog Control by:

A2

COM to C on increasing control signal

Schedule Control by:

W1

-------------------Setpoints------------------

On Schedule:

74.0 Deg F

Alternate On:

0.0 Deg F

Off Schedule:

85.0 Deg F

Off:

0.0 Deg F

Local

Set:

74.0

Deg

F

Selected

by: ....

Dead Band Width +/-: 0.0 Deg F Reverse Action Selc’d when GB5 is ON

Pulse Band Width +/-: 0.0 Deg F

“ “ Off Time:

0 Seconds

“ “ On Time:

0 Seconds

CONTROL ACTION DIAGRAM

<-------COM to H-------> <-----------ALL----------> <-------COM to C------>

ON

PULSED

OFF PULSED

ON

Setpoint

+-------Dead Band--------+

+----------------------------Pulse Band--------------------------+