Tuc setup screen – WattMaster WCC II User Manual

Page 166

background image

Section 3: Screen Descriptions

WCC II Operator’s Guide

Operator Interfaces

3-134

TUC SETUP SCREEN

-----------------------------------------------------------------------------------------

Satellite

#4 TUC

SETUP

#

1 Type:

Relay

Description: Rm 101

Hysteresis: Day 2 x 0.2 Deg Night 5 x 0.2 Deg

Binary

Offset (Deg F)

Deadband

Minimum

Forced

Output

Day

Night

Enabld by Sprd ON Time OFF Time

ON

-----------------------------------------------------------------------------------------

Relay1

0.0(+/-) 10.0(+/-) GB1

1 F 1 min 1 min No

Relay2

2.0(+/-) 12.0(+/-) GB1

1 F 1 min 5 min No

Relay3

0.0(+) 0.0(+) GB0

0 F 0 min 0 min No

------------------------Binary Output Options--------------------------

Relay1

= =>

1. Forced ON if Relay 2 is ON: Yes

2. Forced ON if Relay3 is ON: No

3. Forced OFF during MWU cycle:

No

4. Forced ON if BIN2 is closed: No

5. Forced ON day, cycle night

Relay2

= =>

1. Disabled if BIN2 is closed: No

2. Disabled during MWU cycle: No

3. ON if GB2 is ON

Relay 3

= =>

1. Disabled if BIN2 is closed: No

2. Disabled during MWU cycle: No

3. ON if GB2 is ON

Binary Input Mode: Normal

Override control is Normal, the active time period is 60 minutes.

Run Time Counter: Record total ON Time in minutes for BIN1, reset when GB3 is ON.

Transition Counter: Records total number of transitions from OFF to ON for: None, Reset

when GB3 is ON.

Pneumatic Mode: Pneumatic Driver

Use low resolution on deadband

Deadband is 1 Deg F and pulse-on-time is 0.0/10 seconds

Use proportional mode: No

Reverse action during MWU: No

Forced

bleed:

No

Force

fi ll: No

Use hysteresis on deadband: No

-----------------------------------------------------------------------------------------