Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-27
Satellite #: ____
Specifi es the number of the satellite you are currently editing. If
you would like to edit a different satellite, position the cursor to this
fi eld by using the cursor positioning (arrow) keys, enter the desired
satellite number, and press
.
Trend Log #: ____
This fi eld actually contains two separate fi elds. The fi rst fi eld
specifi es the point “type” (i.e., analog input, control output, analog
output, etc.) and displays the current type in textual form. Because
this is a “choice” fi eld, the list of available choices will be displayed
at the bottom of the screen:
CHOICES:
Make your selection by pressing the
once for each
choice until the desired point type has been selected. (If you select
a point type that is different than that currently being displayed, the
screen will be rewritten with the appropriate screen and data.)
The second fi eld specifi es the point number to edit. For the Trend
Log Screen, this number can range from one to eight. If you would
like to edit a different point, simply position the cursor to this fi eld
by using the cursor positioning (arrow) keys, enter the desired
point number, and press
.
of Type:
Specifi es which of the four available trend logging modes (analog
peak, analog trend, change-of-state, and run time) you wish to use.
Because this is a “choice” fi eld, the list of available choices will be
displayed at the bottom of the screen:
CHOICES:
To make your selection, press the
once for each
choice until the desired mode has been selected, and then press
. (When you select a trend logging mode that is different
than that currently being displayed, the screen will be rewritten
with the appropriate screen and data.)
Records time and date of high & low peaks for:
Specifi es the analog point address for which the analog peaks (high
and low) are to be recorded.
Starting at:
00:00 on 00/00
Specifi es the time and date that the trend log recording should begin.
(The time is represented in 24-hour format.) The system considers
*’s in these positions to be “wild cards.” Therefore, if you want the
system to always log the low and high peaks independent of the
time and dates, enter “*.* on */*.”
Reset by ______ being ____.
Specifi es the [binary] point address that will be used to reset (or
clear) the record trend log data. The fi rst fi eld specifi es the point
address, and the second specifi es the state or condition that the
point address needs to be in in order to clear the data.
Last Low Peak:
00.0 at 00:00 on 00/00
Last High Peak:
00.0 at 00:00 on 00/00
This is the actual trend log data. It is displayed by the system from
information received by the satellite. It details the value of the high
and low peaks and the time and date of their occurrence.
Press
If you want to reset (clear) the existing trend log data, you may do
so by pressing and holding
and then pressing
. After
several seconds this will automatically reset (clear) the data on the
Trend Log Screen (you must leave the screen and come back to it
for the screen to clear). On new systems, each Trend Log Screen
should be reset after it has been programmed to clear out any
“random data” that might be in the satellite controller.
-----------------------------------------------------------------------------------------
Satellite # 1
TREND LOGGING # 1
of Type: ANALOG PEAK
Records time and date of high & low
Starting at: *:* on */*
peaks for: A3
OA TEMP
Reset by: L16 being ON
Last Low Peak:
5.4 Deg F at 5:34 on 12/22
Last High Peak:
98.8 Deg F at 16:56 on 7/04
HOME for menu
-----------------------------------------------------------------------------------------
ANALOG PEAK TREND LOG SCREEN