Section 3: Screen Descriptions

WCC II Operator’s Guide

Operator Interfaces

3-9

Satellite # _______

Specifi es the number of the satellite which you are currently
editing. If you would like to edit a different satellite, use the arrow
keys to move the cursor to this fi eld, type in the desired satellite
number, and press

.

Analog Input # ________

This “fi eld” actually contains two separate fi elds. The fi rst fi eld
specifi es the point “type” (i.e., analog input, control output, analog
output, etc.) and displays the current type in textual form. Because
this is a “choice” fi eld, the list of available choices will be displayed
at the bottom of the screen:

CHOICES:

You may make your selection by pressing the

until

the desired choice appears and then pressing

. (If you select

a point type that is different than that currently being displayed, the
screen will be rewritten with the appropriate screen and data.)

Additionally, this fi eld specifi es the point number to edit. For the
Analog Input Screen, this number can range from one to eight,
corresponding from A1 to A8, respectively. If you would like to
edit a different point, move the cursor to this fi eld by using the
arrow keys, enter the desired point number, and press

.

Description:

A short message is entered here which is displayed on Summary
Screens
to help you remember points within the system. You may
enter up to ten characters (control codes, ALT codes, and the double
quote character are not allowed).

Type:

This fi eld is automatically fi lled in by the system. On screens 2-8,
this will always read “ANALOG.” On screen number 1, it will
read either “ANALOG” or “PULSE” depending on the position of
the pulse switch on the satellite controller.

Satellite # 1

ANALOG INPUT # 1

Description:

RM101

Type:

Analog

Pattern for values associated with this input: xxx.x

Units @ 0% scale:

0.0 Deg F

Units of Measure message #: 1

@ full scale: 100.0 Deg F

Filter Time Constant: 8 seconds

-------------------ALARMS----------------------

Controlled

by:

W1

Limits

Low

High

Alarm Type: 1

On

65.0 80.0 Deg F

Alarm Message #’s:

Low 2 High 1

Off

50.0 100.0 Deg F

Alternate limits selected by: . . . . . . . . . .

On (alt)

0.0

0.0 Deg F

Off

(alt)

0.0

0.0

Deg

F

Limit overlap time

after control change: 20 minutes

Local set

55.0 90.0 Deg F

-------------------BINARY SETPOINT--------------------

OFF Above

0.0 Deg F

On Message #: 0

OFF Below

0.0 Deg F

Off Message #: 0

HOME for menu

-----------------------------------------------------------------------------------------

ANALOG INPUT SCREEN