Analog input screen – WattMaster WCC II User Manual
Page 41
Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-9
Satellite # _______
Specifi es the number of the satellite which you are currently
editing. If you would like to edit a different satellite, use the arrow
keys to move the cursor to this fi eld, type in the desired satellite
number, and press
.
Analog Input # ________
This “fi eld” actually contains two separate fi elds. The fi rst fi eld
specifi es the point “type” (i.e., analog input, control output, analog
output, etc.) and displays the current type in textual form. Because
this is a “choice” fi eld, the list of available choices will be displayed
at the bottom of the screen:
CHOICES:
You may make your selection by pressing the
until
the desired choice appears and then pressing
. (If you select
a point type that is different than that currently being displayed, the
screen will be rewritten with the appropriate screen and data.)
Additionally, this fi eld specifi es the point number to edit. For the
Analog Input Screen, this number can range from one to eight,
corresponding from A1 to A8, respectively. If you would like to
edit a different point, move the cursor to this fi eld by using the
arrow keys, enter the desired point number, and press
.
Description:
A short message is entered here which is displayed on Summary
Screens to help you remember points within the system. You may
enter up to ten characters (control codes, ALT codes, and the double
quote character are not allowed).
Type:
This fi eld is automatically fi lled in by the system. On screens 2-8,
this will always read “ANALOG.” On screen number 1, it will
read either “ANALOG” or “PULSE” depending on the position of
the pulse switch on the satellite controller.
Satellite # 1
ANALOG INPUT # 1
Description:
RM101
Type:
Analog
Pattern for values associated with this input: xxx.x
Units @ 0% scale:
0.0 Deg F
Units of Measure message #: 1
@ full scale: 100.0 Deg F
Filter Time Constant: 8 seconds
-------------------ALARMS----------------------
Controlled
by:
W1
Limits
Low
High
Alarm Type: 1
On
65.0 80.0 Deg F
Alarm Message #’s:
Low 2 High 1
Off
50.0 100.0 Deg F
Alternate limits selected by: . . . . . . . . . .
On (alt)
0.0
0.0 Deg F
Off
(alt)
0.0
0.0
Deg
F
Limit overlap time
after control change: 20 minutes
Local set
55.0 90.0 Deg F
-------------------BINARY SETPOINT--------------------
OFF Above
0.0 Deg F
On Message #: 0
OFF Below
0.0 Deg F
Off Message #: 0
HOME for menu
-----------------------------------------------------------------------------------------
ANALOG INPUT SCREEN