Section 5: Installation Guide
WCC II Operator’s Guide
Operator Interfaces
5-8
The satellite controller must be mounted in an enclosure. If you
do not order the satellite controller with an enclosure, you must
provide your own ventilated enclosure and provide and install your
own fused disconnect switch, transformer, and terminal strip.
The size of the standard enclosure designed to hold one satellite
controller, one fused disconnect switch, one transformer, one fi lter,
and one terminal strip is 15” x 15” x 6.” The size of the standard
enclosure designed to hold two satellite controllers, one fused
disconnect switch, two transformers, two fi lters, and two terminal
strips is 30” x 18” x 6.” If you install the satellite controller
yourself, make sure you leave room for wires to be connected to
the following terminals which are located on the side of the satellite
controller (minimum recommended clearance is 2 inches):
24 VAC power source
Communication loop
Reference voltage
A typical SAT II panel is shown below:
1.
2.
3.