Operator interfaces 3-6 – WattMaster WCC II User Manual
Page 38
Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-6
* These versions of software require the front end computer to
have 448K of RAM memory; later versions require 640K.
** X = 1 to 3 1 = IBM PC or XT
2 = IBM XT 286 3 = 3 satellite system
Alt H for Help
This message is a reminder that the Help Screen can be accessed
by simultaneously pressing
and
. The Help Screen can
be accessed from nearly any screen within the system.
Disk-write-error
If the ECC/WCC II cannot write a fi le to disk because there is
not enough space left on the disk, a “disk-write-error” message
will appear on the Main Menu Screen. To clear the message, go to
the Utility-System Parameter II Screen and select “Yes” after the
“Clear disk_write_error fl ag” statement.
---------------------------------------------
Utility - System Parameter II
Clear disk_write_error fl at:
---------------------------------------------
Message!
This will automatically appear on the screen when a message
has been entered in the Message Screen. To access the Message
Screen, place the cursor over the Utility Screen and press
.
After the Utility Screen appears, place the cursor over Message
Screen and press
again. The screen with the message will
appear.
Active alarms in classes:
If an alarm is active within the system, the alarm type number will
appear at this location. You will need to go to the Alarm Summary
Screen to locate the specifi c alarm.
If the alarm is highlighted, it has not been acknowledged. If the
number is not highlighted, all of the alarms in that class have been
acknowledged.
WCC2 Version _.__
BACKTASK Version _.__
The version number of the software presently being used by the
ECC/WCC II system will appear at these locations. Backtask is a
portion of the ECC/WCC II software. Each version of the WCC2
software operates with a specifi c version of Backtask. This has
been added to insure that the right version of Backtask is operating
with the WCC2 software.
WCC2 Version
Minimum BACKTASK Version
1.47*
1.1B
1.48*
1.1B
1.49*
1.1B
1.52
1.22
1.54
1.24
1.6A
1.24
1.6B
1.24
1.63
1.24
1.64
X.2B**
1.65
X.2BB**
1.67
1.2E
1.68
1.2E
1.69
1.4A
1.70
1.4A
1.71
1.4B
1.72
1.4B
1.74
1.4D