Tuc - control output summary screen – WattMaster WCC II User Manual
Page 160
Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-128
General
The ECC/WCC II looks at the SAT II-A as 4 satellite controllers
and forces the Control Output Screens to be in the EA driver mode
to allow the user to input the following control information from
the Operator Control Console:
Schedule control
Space temperature setpoint
Morning warm-up period
The EA Driver Screen is accessed from the ECC/WCC II System
Main Menu. With the Main Menu showing on the screen, place the
cursor above “Control Outputs” and press
. The Control
Output Summary Screen that is shown above should come into
view.
The EA Driver Summary Screen is slightly different when TUC’s
are used. The status feature is not supported with TUC-R (relay
output only) versions of the TUC. An idle, --> Cool or --> Warm
message will appear here when TUC’s that have either a pneumatic
or stepper motor output are used.
1.
2.
3.
Idle:
This message appears when the actual space temperature
is within the deadband range which is input on the
TUC
Setup Screen #2
.
--> H:
This message appears when the actual temperature is below
the deadband range which is input on the
TUC Setup
Screen #2
.
--> C:
This message appears when the actual temperature is above
the deadband range which is input on the
TUC Setup
Screen #2
.
TUC - CONTROL OUTPUT SUMMARY SCREEN
-----------------------------------------------------------------------------------------
Control Output Summary Screen
Control
Out
Satellite
4
Time
Date
---------Control
Outputs---------
17:07
7/07
SCHED ANALOG CONTROL LIMIT
COMMENTS STATUS STATUS MODE CONTROL INPUT LOW HIGH
K1 : TUC 4.1
idle +W
72.4
Setpoint = 72
K2:
TUC 4.2
idle +W
71.8
Setpoint = 72
K3:
K4:
K5:
K6:
K7:
K8:
-----------------------------------------------------------------------------------------