Analog trend trend log screen – WattMaster WCC II User Manual
Page 60
Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-28
Satellite #: ____
Specifi es the number of the satellite you are currently editing.
If you would like to edit a different satellite, simply position the
cursor to this fi eld by using the cursor positioning (arrow) keys,
enter the desired satellite number, and press
.
Trend Log #: ____
This fi eld actually contains two separate fi elds. The fi rst fi eld
specifi es the point “type” (i.e., analog input, control output, analog
output, etc.) and displays the current type in textual form. Because
this is a “choice” fi eld, the list of available choices will be displayed
at the bottom of the screen:
CHOICES:
To make your selection, press the
once for each
choice until the desired point type has been selected. (If you select
a point type that is different than that currently being displayed, the
screen will be rewritten with the appropriate screen and data. The
second fi eld specifi es the point number to edit. For the Trend Log
Screen, this number can range from one to eight. If you would like
to edit a different point, simply position the cursor to this fi eld by
using the cursor positioning (arrow) keys, enter the desired point
number, and press
.
of Type:
Specifi es which of the four available trend logging modes (analog
peak, analog trend, change-of-state, and run time) you wish to use.
Because this is a “choice” fi eld, the list of available choices will be
displayed at the bottom of the screen:
CHOICES:
Make your selection by pressing the
choice until the desired mode has been selected, and then press
. (When you select a trend logging mode that is different
than that currently being displayed, the screen will be rewritten
with the appropriate screen and data.)
-----------------------------------------------------------------------------------------
Satellite # 1
TREND LOGGING # 1
of Type: ANALOG TREND
Records value of: A1
RM101
Starting at: *:* on */*
once every: 1 Minute
Reset by: L16 being ON
Roll after 48 readings
16:32
7/07 75.5 16:48
7/07
73.8
17:04
7/07
73.9
16:33
7/07 75.4 16:49
7/07
73.8
17:05
7/07
73.9
16:34
7/07 75.4 16:50
7/07
73.8
17:06
7/07
73.9
16:35
7/07 75.4 16:51
7/07
73.7
17:07
7/07
73.9
16:36
7/07 75.4 16:52
7/07
73.7
17:08
7/07
73.9
16:37
7/07 75.3 16:53
7.07
73.7
17:09
7/07
73.9
16:38
7/07 75.2 16:54
7/07
73.7
17:10
7/07
73.9
16:39
7/07 75.0 16:55
7/07
73.6
17:11
7/07
73.9
16:40
7/07 74.8 16:56
7/07
73.6
17:12
7/07
73.9
16:41
7/07 74.6 16:57
7/07
73.6
17:13
7/07
73.9
16:42
7/07 74.4 16:58
7/07
73.6
17:14
7/07
73.9
16:43
7/07 74.3 16:59
7/07
73.7
17:15
7/07
73.9
16:44
7/07 74.2 17:00
7/07
73.7
17:16
7/07
73.9
16:45
7/07 74.0 17:01
7/07
73.8
17:17
7/07
73.9
16:46
7/07 73.9 17:02
7/07
73.8
17:18
7/07
73.9
16:47
7/07 73.9 17:03
7/07
73.8
17:19
7/07
73.9
HOME for menu
-----------------------------------------------------------------------------------------
ANALOG TREND TREND LOG SCREEN