Analog input summary screen – WattMaster WCC II User Manual
Page 39
Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-7
An analog input is a signal sent to the satellite controller that can
be represented by a number such as temperature, pressure, etc. The
Analog Input Screen is used to “tell” the ECC/WCC II system the
characteristics of the sensor and to set alarm limits. The “Binary
Setpoint” option at the bottom of the Analog Input Screen can be
used to convert the analog input to a binary (On/Off) input.
Analog Inputs
Specifi es the summary type to be displayed. Because this is a
“choice” fi eld, the list of available choices will be displayed at the
bottom of the screen:
CHOICES:
You can access one of the screens which appear in this choice fi eld
without returning to the Main Menu by pressing the
until the desired summary type has been selected and then pressing
.
Satellite______
Specifi es the number of the satellite which you are currently
communicating with. If you would like to view the analog input
summary data for a different satellite, use the arrow keys to move
the cursor to this fi eld, enter the desired satellite number, and press
.
To view or edit a specifi c analog input, use the arrow keys to move
the cursor (shown as “>” along the left-hand side of the screen) to
the desired point and press
. The Analog Input Screen for
the specifi ed point will now appear.
Time Date
The present time and date will automatically appear at these
locations.
Description:_______________
The description message which was entered on the Analog Input
Screen is displayed here to help you identify the different analog
inputs within the system.
ANALOG INPUT SUMMARY SCREEN
-----------------------------------------------------------------------------------------
Analog Inputs
Satellite 1 Time
Date
-------------------Analog Inputs----------------------------- 14:17 7/07
Description
Current Value
Alarm Limits
Stat Mode
Alarm Details
A1: RM101
74.7 Deg F
65.0 80.0
ON
A2: SA TEMP
54.6 Deg F
45.0 65.0
OFF
A3: OA TEMP
89.8 Deg F -10.0 100.0
ON
A4: DOCK TEMP
85.0 Deg F
45.0 100.0
ON
A5:
A6:
A7:
A8:
C1:
OFF
C2:
OFF
C3: CHW
OFF
C4:
OFF
C5:
C6:
C7:
C8: