beautypg.com

Analog input summary screen – WattMaster WCC II User Manual

Page 39

background image

Section 3: Screen Descriptions

WCC II Operator’s Guide

Operator Interfaces

3-7

An analog input is a signal sent to the satellite controller that can
be represented by a number such as temperature, pressure, etc. The
Analog Input Screen is used to “tell” the ECC/WCC II system the
characteristics of the sensor and to set alarm limits. The “Binary
Setpoint” option at the bottom of the Analog Input Screen can be
used to convert the analog input to a binary (On/Off) input.

Analog Inputs

Specifi es the summary type to be displayed. Because this is a
“choice” fi eld, the list of available choices will be displayed at the
bottom of the screen:

CHOICES:

You can access one of the screens which appear in this choice fi eld
without returning to the Main Menu by pressing the

until the desired summary type has been selected and then pressing

.

Satellite______

Specifi es the number of the satellite which you are currently
communicating with. If you would like to view the analog input
summary data for a different satellite, use the arrow keys to move
the cursor to this fi eld, enter the desired satellite number, and press

.

To view or edit a specifi c analog input, use the arrow keys to move
the cursor (shown as “>” along the left-hand side of the screen) to
the desired point and press

. The Analog Input Screen for

the specifi ed point will now appear.

Time Date

The present time and date will automatically appear at these
locations.

Description:_______________

The description message which was entered on the Analog Input
Screen
is displayed here to help you identify the different analog
inputs within the system.

ANALOG INPUT SUMMARY SCREEN

-----------------------------------------------------------------------------------------

Analog Inputs

Satellite 1 Time

Date

-------------------Analog Inputs----------------------------- 14:17 7/07

Description

Current Value

Alarm Limits

Stat Mode

Alarm Details

A1: RM101

74.7 Deg F

65.0 80.0

ON

A2: SA TEMP

54.6 Deg F

45.0 65.0

OFF

A3: OA TEMP

89.8 Deg F -10.0 100.0

ON

A4: DOCK TEMP

85.0 Deg F

45.0 100.0

ON

A5:

A6:

A7:

A8:

C1:

OFF

C2:

OFF

C3: CHW

OFF

C4:

OFF

C5:

C6:

C7:

C8:

HOME for menu

-----------------------------------------------------------------------------------------