Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-127
The TUC is designed to use the same 2 or 3-wire, fl ush-mounted
space temperature sensor that is used with the SAT II controllers.
The space temperature sensor is wired directly to the TUC.
The
Analog Input Screens are used to scale the values of the
temperature sensors connected to the TUC’s. The TUC is limited to
reading a temperature from 45 ºF to 96.2 ºF. Therefore, the scaling
values on the Analog Input Screen need to be set up as follows:
Units
@ 0% scale:
45.0 ºF
@ full scale:
96.2 ºF
The other inputs on the Analog Input Screen are set up the same as
for a SAT II controller.
TUC - ANALOG INPUT SCREEN
-----------------------------------------------------------------------------------------
Satellite # 1
ANALOG INPUT # 1
Description:
RM101
Type:
Analog
Pattern for values associated with this input: xxx.x
Units @ 0% scale: 45.0 Deg F Units of Measure message #: 1
@ full scale: 96.2 Deg F Filter Time Constant: 8 seconds
----------------------ALARMS-----------------------
Controlled
by:
W1
Limits
Low
High
Alarm Type: 1
On
65.0 80.0 Deg F
Alarm Message #’s: Low 2 High 1
Off
50.0 100.0 Deg F
Alternate limits selected by: ........
On (alt)
0.0
0.0 Deg F
Off (alt)
0.0
0.0 Deg F
Limit overlap time after
control change: 20 Minutes
Local set
55.0 90.0 Deg F
-----------------------BINARY SETPOINT-------------------------
OFF Above
0.0 Deg F
On Message #: 0
OFF Below
0.0 Deg F
Off Message #: 0
HOME for menu
-----------------------------------------------------------------------------------------