Section 5: Installation Guide

WCC II Operator’s Guide

Operator Interfaces

5-33

Addressing (Numbering) the SAT II-B

In order for the ECC/WCC II system to communicate properly with
each SAT II-B, each SAT II-B must be assigned a separate number
(address). The number is assigned by positioning the small toggle
switches on the front of the SAT II-B in the proper position. The
toggle switches are housed together in a block as shown below:

When the switch is in the ON position, it represents the number on
the right in the drawing. That is, when switch 4 is ON, and all of the
other switches are OFF, the SAT II-B is addressed (named) #4. The
switches are additive. That is to say, when switches 4 and 8 are ON,
and all of the other switches are OFF, the SAT II-B is addressed
#12. The SAT II-B looks at the position of the switch setting during
its power-up cycle. If you need to readdress a SAT II-B, you must
change the switch settings, turn off the power to the SAT II-B, and
then turn the SAT II-B back on again.

When the LOCAL switch is in the ON position, the TUC’s will
operate according to their “local set” setpoints. That is, the TUC’s
will operate as if the front end computer is off-line, but the SAT
II-B is still present.

The test mode is active if the TEST switch is in the ON position.
The word “TEST” can be input as the binary value on the EA
Driver Screen
to select the alternate setpoints. When you want
to check the operation of the alternate setpoints, place the TEST
switch in the ON position.