beautypg.com

Analog global screen – WattMaster WCC II User Manual

Page 94

background image

Section 3: Screen Descriptions

WCC II Operator’s Guide

Operator Interfaces

3-62

Global #:____

Specifi es the global number and its type. Because this is a “choice”
fi eld, the list of available choices will be displayed at the bottom
of the screen:

CHOICES:

Make your selection by pressing the

once for each

choice until the desired global type has been selected, and then
press

. (If you select a global type that is different than

that currently being displayed, the screen will be rewritten with the
appropriate screen information.)

If you would like to edit a different global, simply position the
cursor to this fi eld by using the cursor positioning (arrow) keys,
entering the desired global number, and pressing

.

name is ______

Specifi es the name (point address) of this analog global. Any
changes to the global number will be refl ected in this point address
(e.g., ANALOG GLOBAL #: 28 would show GA 28 as the
name).

Description: ________________

Specifi es a short message which is displayed on Summary and Data
Entry/Editing Screens
to aid you in remembering points within the
system. You may enter up to 20 characters (control, codes, ALT
codes, and the double quote character are not allowed).

Data Pattern: _____

Specifi es the number of signifi cant digits for analog global values
displayed by the system. Because this is a “choice” fi eld, the list of
available choices will be displayed at the bottom of the screen:

CHOICES:

Units of Measure:

Specifi es a message number to be used throughout the system to
reference a textual message which is displayed with the values
associated with this global. For example, if units of measure
message #4 is Deg F, and the units of measure message for the
specifi c analog global is degrees Fahrenheit, then the units of
measure would be 4.

In Local Set this global defaults to

Because this is a “choice” fi eld, the list of available choices will be
displayed at the bottom of the screen:

CHOICES:

Make your selection by pressing the

once for each

choice until the desired default choice has been selected, and then
press

.

ANALOG GLOBAL SCREEN

-----------------------------------------------------------------------------------------

Description:

GLOBAL ANALOG # 1

Data Pattern:

xxx.x

Unit

of

Measure:

1

In Local Set this global defaults to FIXED value of: 74

Mode

1:

Averaged

List

Values to be averaged

5A4

7A6

22A1 13A3 ____ ____ ____ ____

Substitute 72 for each unavailable value until more than 3 values are unavailable, then

use 70 as the value for this global.

Range

Low Limit

High Limit

Type Message #

Message

Inside

0.0

0.0

0

0

-----------------------------------------------------------------------------------------