beautypg.com

WattMaster WCC II User Manual

Page 62

background image

Section 3: Screen Descriptions

WCC II Operator’s Guide

Operator Interfaces

3-30

The system will search seven days from the date showing on the
data screen. If you want to search seven more days, press

or

again.

You may want to periodically make back-up copies of the analog
trend data fi les and then delete the trend log fi les to avoid over-
fi lling the data disk. The trend log data fi les are saved using the
following format:

001T2708.321

001 -> Satellite number (001-240)
T -> Always T, for analog trend log
2 -> Analog Trend Log # (1-8)
7 -> Last digit of the year (i.e. 1987 = 7)
08 -> Hour that the trend log was saved (0-23)
3 -> Month in Hex Code (1-C)
21 -> Day of the Month that the trend log was saved (1-31)

Press to Reset Data

If you want to reset (clear) the existing trend log data, you may
do so by pressing and holding

and then typing

. After

several seconds this will automatically reset (clear) the data on the
Trend Log Screen (you must leave the screen and come back to it
for the screen to clear). On new systems, each Trend Log Screen
should be reset after it has been programmed to clear out any
“random data” that might be in the satellite controller.