WattMaster WCC II User Manual
Page 62
Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-30
The system will search seven days from the date showing on the
data screen. If you want to search seven more days, press
or
again.
You may want to periodically make back-up copies of the analog
trend data fi les and then delete the trend log fi les to avoid over-
fi lling the data disk. The trend log data fi les are saved using the
following format:
001T2708.321
001 -> Satellite number (001-240)
T -> Always T, for analog trend log
2 -> Analog Trend Log # (1-8)
7 -> Last digit of the year (i.e. 1987 = 7)
08 -> Hour that the trend log was saved (0-23)
3 -> Month in Hex Code (1-C)
21 -> Day of the Month that the trend log was saved (1-31)
Press
If you want to reset (clear) the existing trend log data, you may
do so by pressing and holding
and then typing
. After
several seconds this will automatically reset (clear) the data on the
Trend Log Screen (you must leave the screen and come back to it
for the screen to clear). On new systems, each Trend Log Screen
should be reset after it has been programmed to clear out any
“random data” that might be in the satellite controller.