Satellite summary screen – WattMaster WCC II User Manual
Page 70
Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-38
Sat #:
Twenty satellites will appear on each Satellite Summary Screen.
If your system has more than twenty satellites, to view the next
twenty satellites, simply press
(Page Down) located on
the keypad to the right of the keyboard. To view the previous
twenty satellites, simply press
(Page Up) also located on
the keypad.
When fi rst entering this Satellite Summary Screen, you will
experience a slight delay in acquiring information on the screen.
This is because the system needs to travel the entire communication
loop to gather the information needed for this particular segment
of the program.
Location:
This location is a user entered message which may pertain to the
name of the satellite, the location of the satellite, etc.
If you are adding satellites to an existing system, you will not see
the new satellites on this screen until you have rebuilt the data
tables for these satellites. With any new hardware additions (adding
new satellites, optional boards, etc.), you MUST rebuild the table
for the particular satellite controller using the new hardware. Also,
whenever you receive and install a new version of ECC/WCC II
software, you MUST rebuild the ENTIRE table for the ENTIRE
system. For further information on rebuilding the table for the
system, consult the Special Purpose Keys section on page 3-1 of
this guide.
Power-Up Delay:
This feature allows the ECC/WCC II system to soft-start a building
after a main power failure. If power is lost to the building, the
satellites cannot control any of the equipment because everything
will be off. When power is restored, the binary output contacts on
the satellite controller will remain open for the power up delay
time, thus holding the equipment off. You may want to bring on a
critical satellite fi rst (lighting) and less critical satellites later.
-----------------------------------------------------------------------------------------
Satellite
Summary
Time
Date
Sat #
Location
Power-Up
Alarms
11:54
7/21
Delay
by-class
LOC
TST
TYPE
VER
ERR
1
Satellite #1 10
Seconds
12345678
II
1.06
2
Satellite #2
3 Minutes
12345678
II
1.06
3
SOS
4
Non-Existent
5
Non-Existent
6
Non-Existent
7
Non-Existent
8
Non-Existent
9
Non-Existent
10
Non-Existent
11
Non-Existent
12
Non-Existent
13
Non-Existent
14
Non-Existent
15
Non-Existent
16
Non-Existent
17
Non-Existent
18
Non-Existent
19
Non-Existent
20
Non-Existent
HOME for menu
-----------------------------------------------------------------------------------------