Section 3: Screen Descriptions

WCC II Operator’s Guide

Operator Interfaces

3-40

This screen allows you to override addresses within the system for
programmable time periods. The allowable choices for override
type depend on the password level.

With Level 1 Password, choices are
With Level 2 Password, choices are With Level 3 Password, choices are

ADDRESS

This is a user entered fi eld which initiates the Override program of
the ECC II/WCC II system. Addresses which may be used on this
screen are shown below:

#An - Analog Input
#Pn - Analog Output
#KnH - Control Output (H Contact)
#KnC - Control Output (C contact)
Wn - Week Schedule
Sn - Optimal Start
GBn - Binary Global
GAn - Analog Global

Type/Value

The Type or Value of the address is entered in this position. A
binary type of address will have a type of either being ON or OFF.
An analog address will have a numerical value such as °F, PSI,
KW, % Sun, etc.

----- Start

-----

----- End

-----

The Start and End portion of the program is where you enter the
Time, Month, and Day for the override to occur. If you enter a start
time later than the present time, the override will erase itself from
the screen after the override has been completed.

-----------------------------------------------------------------------------------------

OVERRIDES

-----------Start----------- ------------End------------

ADDRESS

Type/Value

TIME MONTH

DAY

TIME MONTH DAY

W12

Off

745

2

15

845

2

15

S5

Off

745

2

15

845

2

15

GB9

On

745

2

15

845

2

15

GA15 72.5 Deg F

950

2

16

1200 2

17

GA10 30.0 Deg F

1130 3

17

2200 3

18

184K2C Schd On

900

4

11

1500 4

14

HOME for menu

-----------------------------------------------------------------------------------------

OVERRIDE SCREEN