Override screen – WattMaster WCC II User Manual
Page 72
Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-40
This screen allows you to override addresses within the system for
programmable time periods. The allowable choices for override
type depend on the password level.
With Level 1 Password, choices are
With Level 2 Password, choices are
ADDRESS
This is a user entered fi eld which initiates the Override program of
the ECC II/WCC II system. Addresses which may be used on this
screen are shown below:
#An - Analog Input
#Pn - Analog Output
#KnH - Control Output (H Contact)
#KnC - Control Output (C contact)
Wn - Week Schedule
Sn - Optimal Start
GBn - Binary Global
GAn - Analog Global
Type/Value
The Type or Value of the address is entered in this position. A
binary type of address will have a type of either being ON or OFF.
An analog address will have a numerical value such as °F, PSI,
KW, % Sun, etc.
----- Start
-----
----- End
-----
The Start and End portion of the program is where you enter the
Time, Month, and Day for the override to occur. If you enter a start
time later than the present time, the override will erase itself from
the screen after the override has been completed.
-----------------------------------------------------------------------------------------
OVERRIDES
-----------Start----------- ------------End------------
ADDRESS
Type/Value
TIME MONTH
DAY
TIME MONTH DAY
W12
Off
745
2
15
845
2
15
S5
Off
745
2
15
845
2
15
GB9
On
745
2
15
845
2
15
GA15 72.5 Deg F
950
2
16
1200 2
17
GA10 30.0 Deg F
1130 3
17
2200 3
18
184K2C Schd On
900
4
11
1500 4
14
HOME for menu
-----------------------------------------------------------------------------------------
OVERRIDE SCREEN