Section 3: Screen Descriptions

WCC II Operator’s Guide

Operator Interfaces

3-17

Satellite #: _____

Specifi es the number of the satellite you are currently editing. If
you would like to edit a different satellite, use the arrow keys to
move the cursor to this fi eld, enter the desired satellite number, and
press

.

Control Output _____

This fi eld actually contains two separate fi elds. The fi rst fi eld
specifi es the point “type” (i.e., analog input, control output, analog
output, etc.) and displays the current type in textual form. Because
this is a “choice” fi eld, the list of available choices will be displayed
at the bottom of the screen:

CHOICES:

You may make your selection by pressing the

once

for each choice, until the desired point type has been selected. (If
you select a point type that is different than that currently being
displayed, the screen will be rewritten with the appropriate screen
and data.) The second fi eld specifi es the point number to edit. For
the Control Output Screen, this number can range from one to
eight. If you would like to edit a different point, simply position

the cursor to this fi eld by using the cursor positioning (arrow) keys,
enter the desired point number, and press

.

Mode: ____________

Specifi es the mode type of the output contact. Because this is a
“choice” fi eld, the list of available choices will be displayed at the
bottom of the screen:

CHOICES:

You may make your selection by pressing the

once

for each choice, until the desired point type has been selected, and
then pressing

. (If you select a mode type that is different

than that currently being displayed, the screen will be rewritten
with the appropriate screen information.

_______ Contact

Specifi es which of the two available contacts per point (H or C)
to confi gure. Because this is a “choice” fi eld, the list of available
choices will be displayed at the bottom of the screen:

CHOICES:

-----------------------------------------------------------------------------------------

Satellite # 1

CONTROL OUTPUT 1

Mode: Dual Limit

-------------- C Contact --------------

Description: HP COMP

Contact Open Message #: 2 Off

Analog Control by: A5

Contact Closed Message #: 1 On

Schedule Control by: W1

Minimum Off Time: 3 Minutes

Alt Mode Selected by: . . . .

Minimum On Time: 3 Minutes

Override OPEN when . . . . is ON

Hysteresis: +/- 5 x 0.1 Deg F

Low

Limit

Hi

Limit

Local Set

OPEN

Between 70.0 & 76.0 Deg F

On Schedule

OPEN

Between 70.0 & 76.0 Deg F

Off

Schedule

OPEN

Between 60.0 & 80.0 Deg F

On Schedule (alt) OPEN

Between 0.0 & 0.0 Deg F

Off Schedule (alt) OPEN

Between 0.0 & 0.0 Deg F

Data Register is measured from Midpoint and Refl ects Hysteresis

HOME for menu

----------------------------------------------------------------------------------------

DUAL LIMIT SCREEN