Dual limit screen – WattMaster WCC II User Manual
Page 49
Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-17
Satellite #: _____
Specifi es the number of the satellite you are currently editing. If
you would like to edit a different satellite, use the arrow keys to
move the cursor to this fi eld, enter the desired satellite number, and
press
.
Control Output _____
This fi eld actually contains two separate fi elds. The fi rst fi eld
specifi es the point “type” (i.e., analog input, control output, analog
output, etc.) and displays the current type in textual form. Because
this is a “choice” fi eld, the list of available choices will be displayed
at the bottom of the screen:
CHOICES:
You may make your selection by pressing the
once
for each choice, until the desired point type has been selected. (If
you select a point type that is different than that currently being
displayed, the screen will be rewritten with the appropriate screen
and data.) The second fi eld specifi es the point number to edit. For
the Control Output Screen, this number can range from one to
eight. If you would like to edit a different point, simply position
the cursor to this fi eld by using the cursor positioning (arrow) keys,
enter the desired point number, and press
.
Mode: ____________
Specifi es the mode type of the output contact. Because this is a
“choice” fi eld, the list of available choices will be displayed at the
bottom of the screen:
CHOICES:
You may make your selection by pressing the
once
for each choice, until the desired point type has been selected, and
then pressing
. (If you select a mode type that is different
than that currently being displayed, the screen will be rewritten
with the appropriate screen information.
_______ Contact
Specifi es which of the two available contacts per point (H or C)
to confi gure. Because this is a “choice” fi eld, the list of available
choices will be displayed at the bottom of the screen:
CHOICES:
-----------------------------------------------------------------------------------------
Satellite # 1
CONTROL OUTPUT 1
Mode: Dual Limit
-------------- C Contact --------------
Description: HP COMP
Contact Open Message #: 2 Off
Analog Control by: A5
Contact Closed Message #: 1 On
Schedule Control by: W1
Minimum Off Time: 3 Minutes
Alt Mode Selected by: . . . .
Minimum On Time: 3 Minutes
Override OPEN when . . . . is ON
Hysteresis: +/- 5 x 0.1 Deg F
Low
Limit
Hi
Limit
Local Set
OPEN
Between 70.0 & 76.0 Deg F
On Schedule
OPEN
Between 70.0 & 76.0 Deg F
Off
Schedule
OPEN
Between 60.0 & 80.0 Deg F
On Schedule (alt) OPEN
Between 0.0 & 0.0 Deg F
Off Schedule (alt) OPEN
Between 0.0 & 0.0 Deg F
Data Register is measured from Midpoint and Refl ects Hysteresis
HOME for menu
----------------------------------------------------------------------------------------
DUAL LIMIT SCREEN