If you ordered a V-out board which has more than one pair of
potentiometers to allow you to have different changeover and
hysteresis setpoints for the binary outputs, the potentiometers are
labeled as follows:
To understand the V-out board better, consider a changeover
setpoint of 7.5 VDC with a hysteresis of 1 VDC. The chip switch
on the V-out board will open when the voltage is 8 VDC and will
not close until the voltage drops to 7 VDC. Assume the Analog
Input Screen on the ECC/WCC II system is set up according to the
following parameters:
Changeover Setpoint
Hysteresis
----------------------- ---------------------------
Binary Output
Potentiometer
Label
Potentiometer
Label
------------- ------------- -------- -------------- -----------
1
R19
“SET
1”
R9
“DELTA
1”
2
R20
“SET
2”
R10
“DELTA
2”
3
R21
“SET
3”
R11
“DELTA
3”
4
R22
“SET
4”
R12
“DELTA
4”
5
R23
“SET
5”
R13
“DELTA
5”
6
R24
“SET
6”
R14
“DELTA
6”
7
R25
“SET
7”
R15
“DELTA
7”
8
R26
“SET
8”
R16
“DELTA
8”
Output = 0.0 volts DC when the Space Temperature = 65 Deg F
Output = 15.0 volts DC when the Space Temperature = 80 Deg F
Space Temperature
Voltage Supplied to
(°F)
the
V-out
Board
-----------------------
---------------------
65
0.0
---------------------------
66
1.0
67
2.0
68
3.0 Chip Switch Closed
69
4.0
70
5.0
71
6.0
72
7.0
---------------------------
72.5 Setpoint
7.5 Hysteresis
73
8.0
---------------------------
74
9.0
75
10.0
76
11.0 Chip Switch Open
77
12.0
78
13.0
79
14.0
80
15.0
---------------------------