beautypg.com

WattMaster WCC II User Manual

Page 221

background image

Section 5: Installation Guide

WCC II Operator’s Guide

Operator Interfaces

5-19

If you ordered a V-out board which has more than one pair of
potentiometers to allow you to have different changeover and
hysteresis setpoints for the binary outputs, the potentiometers are
labeled as follows:

To understand the V-out board better, consider a changeover
setpoint of 7.5 VDC with a hysteresis of 1 VDC. The chip switch
on the V-out board will open when the voltage is 8 VDC and will
not close until the voltage drops to 7 VDC. Assume the Analog
Input Screen
on the ECC/WCC II system is set up according to the
following parameters:

Changeover Setpoint

Hysteresis

----------------------- ---------------------------

Binary Output

Potentiometer

Label

Potentiometer

Label

------------- ------------- -------- -------------- -----------

1

R19

“SET

1”

R9

“DELTA

1”

2

R20

“SET

2”

R10

“DELTA

2”

3

R21

“SET

3”

R11

“DELTA

3”

4

R22

“SET

4”

R12

“DELTA

4”

5

R23

“SET

5”

R13

“DELTA

5”

6

R24

“SET

6”

R14

“DELTA

6”

7

R25

“SET

7”

R15

“DELTA

7”

8

R26

“SET

8”

R16

“DELTA

8”

Output = 0.0 volts DC when the Space Temperature = 65 Deg F

Output = 15.0 volts DC when the Space Temperature = 80 Deg F

Space Temperature

Voltage Supplied to

(°F)

the

V-out

Board

-----------------------

---------------------

65

0.0

---------------------------

66

1.0

67

2.0

68

3.0 Chip Switch Closed

69

4.0

70

5.0

71

6.0

72

7.0

---------------------------

72.5 Setpoint

7.5 Hysteresis

73

8.0

---------------------------

74

9.0

75

10.0

76

11.0 Chip Switch Open

77

12.0

78

13.0

79

14.0

80

15.0

---------------------------