Analog global- look up table screen – WattMaster WCC II User Manual

Page 110

background image

Section 3: Screen Descriptions

WCC II Operator’s Guide

Operator Interfaces

3-78

ANALOG GLOBAL-

LOOK UP TABLE SCREEN

-----------------------------------------------------------------------------------------

ANALOG Global #: 121

Name is GA121

Description: Temperature

Data Pattern: xxx.x

Unit

of

Measure:

1

°F

In Local Set this global defaults to LAST VALUE

Analog Input: 2A3

Extend Data to Next Table?: NO

Mode 5: Look Up Table

If the input data is unavailable, then use 70 as default value

IN OUT

IN

OUT

IN

OUT

IN

OUT

1: 41 -> 41.5 16: 56 -> 59.5

31: 71 -> 68.0 46: 86 -> 78.0

2: 42 -> 42.5 17: 57 -> 60.3

32: 72 -> 68.5 47: 87 -> 78.7

3: 43 -> 44.5 18: 58 -> 61.0

33: 73 -> 69.0 48: 88 -> 79.7

4: 44 -> 46.5 19: 59 -> 61.5

34: 74 -> 69.5 49: 89 -> 80.7

5: 45 -> 47.5 20: 60 -> 62.0

35: 75 -> 70.0 50: 90 -> 81.7

6: 46 -> 49.0 21: 61 -> 62.5

36: 76 -> 70.6 51: 91 -> 83.0

7: 47 -> 51.5 22: 62 -> 63.0

37: 77 -> 71.3 52: 92 -> 84.0

8: 48 -> 51.8 23: 63 -> 63.5

38: 78 -> 72.0 53: 93 -> 85.3

9: 49 -> 53.0 24: 64 -> 64.0

39: 79 -> 72.5 54: 94 -> 86.5

10: 50 -> 54.0 25: 65 -> 64.8

40: 80 -> 73.0 55: 95 -> 88.0

11: 51 -> 55.0 26: 66 -> 65.5

41: 81 -> 74.0 56: 96 -> 89.5

12: 52 -> 56.3 27: 67 -> 66.0

42: 82 -> 74.5 57: 97 -> 91.0

13: 53 -> 57.0 28: 68 -> 66.3

43: 83 -> 75.3 58: 98 -> 93.0

14: 54 -> 58.0 29: 69 -> 67.0

44: 84 -> 76.0 59: 99 -> 95.5

15: 55 -> 59.0 30: 70 -> 67.3

45: 85 -> 77.0 60: 100 -> 100.0