beautypg.com

Tuc-vr analog input screen – WattMaster WCC II User Manual

Page 179

background image

Section 3: Screen Descriptions

WCC II Operator’s Guide

Operator Interfaces

3-147

The TUC-VR is designed to use either the 4-wire WRS-1FVR fl ush
mount temperature sensor or the 4-wire TRS-VR room thermostat.
The space temperature sensor or thermostat is wired directly to the
TUC-VR.

The Analog Input Screens are used to scale the values of the
temperature sensors. The TUC-VR is limited to reading a
temperature from 40 °F to 95 °F. However, the scaling values on
the Analog Input Screen must be set up as shown below:

Units @ 0% scale:

0 Deg F

@ full scale: 100 Deg F

The other inputs on the Analog Input Screen are set up the same as
for a SAT II controller with the exception of the data pattern value
always being forced to x,xxx.

TUC-VR ANALOG INPUT SCREEN

-----------------------------------------------------------------------------------------

Satellite # 1

ANALOG INPUT # 1

Description:

RM101

Type:

Analog

Pattern for values associated with this input: x,xxx

Units @ 0% scale:

0 Deg F

Units of Measure message #: 1

@ full scale:

100 Deg F

Filter Time Constant: 8 seconds

--------------------------ALARMS---------------------------

Controlled

by:

W1

Limits

Low

High

Alarm Type: 1

On

65

80 Deg F

Alarm Message #’s: Low 2

High 1

Off

50

100 Deg F

Alternate limits selected by: ....

On (alt)

0

0 Deg F

Off (alt)

0

0 Deg F

Limit overlap time

after control change: 20 Minutes

Local set

55

90 Deg F

-----------------------------BINARY SETPOINT------------------------

OFF Above

0 Deg F

On Message #:

0

OFF Below

0 Deg F

Off Message #:

0