Tuc-vr analog input screen – WattMaster WCC II User Manual
Page 179
Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-147
The TUC-VR is designed to use either the 4-wire WRS-1FVR fl ush
mount temperature sensor or the 4-wire TRS-VR room thermostat.
The space temperature sensor or thermostat is wired directly to the
TUC-VR.
The Analog Input Screens are used to scale the values of the
temperature sensors. The TUC-VR is limited to reading a
temperature from 40 °F to 95 °F. However, the scaling values on
the Analog Input Screen must be set up as shown below:
Units @ 0% scale:
0 Deg F
@ full scale: 100 Deg F
The other inputs on the Analog Input Screen are set up the same as
for a SAT II controller with the exception of the data pattern value
always being forced to x,xxx.
TUC-VR ANALOG INPUT SCREEN
-----------------------------------------------------------------------------------------
Satellite # 1
ANALOG INPUT # 1
Description:
RM101
Type:
Analog
Pattern for values associated with this input: x,xxx
Units @ 0% scale:
0 Deg F
Units of Measure message #: 1
@ full scale:
100 Deg F
Filter Time Constant: 8 seconds
--------------------------ALARMS---------------------------
Controlled
by:
W1
Limits
Low
High
Alarm Type: 1
On
65
80 Deg F
Alarm Message #’s: Low 2
High 1
Off
50
100 Deg F
Alternate limits selected by: ....
On (alt)
0
0 Deg F
Off (alt)
0
0 Deg F
Limit overlap time
after control change: 20 Minutes
Local set
55
90 Deg F
-----------------------------BINARY SETPOINT------------------------
OFF Above
0 Deg F
On Message #:
0
OFF Below
0 Deg F
Off Message #:
0