The messages under the “Current State” heading will refl ect the
changes.
Unoccupied: If you force the zone to the unoccupied
mode, the system will put a zero (always
OFF) in the “Schedule Selected by” input on
the Control Output Screen for that zone.
Occupied: If you force the zone to the occupied mode,
the system will insert a 1 (always ON) in the
“Schedule Selected by” input on the Control
Output Screen for that zone.
Automatic: If you select automatic, the system will
restore the input in the “Schedule Selected
by” fi eld of the Control Output Screen to its
normal schedule (i.e. W1).
Logical Address: 7k1h
The logical address of the control output for the zone in question is
shown here in the form of 7k1h.
7 => The satellite number (1-250).
k => Control Output (always k).
1 => Satellite Controller Channel (1-8).
h => The load is connected to either the COM & H or
COM & C terminals on the satellite (h or c).
“7k1h” means that the piece of equipment serving the zone in
question is connected to the COM and H terminals on channel
number 1 of satellite controller #7.