WattMaster WCC II User Manual
Page 69
Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-37
Clearing Random Data in Satellite
Run Time Registers
You may see some blank lines between two actual alarms on the
Alarm Summary Screen the fi rst time the ECC/WCC II system is
brought on line. These blank lines are caused by random data in
a satellite run time register the fi rst time a satellite controller is
powered up. If these registers are not cleared, the speed at which
the ECC/WCC II system can move from screen to screen will be
much slower.
To fi nd which satellite run time registers need to be reset, use the
arrow keys to move the cursor to one of the blank lines on the
Alarm Summary Screen and press
. The Run Time Screen
that needs to be reset will appear on the screen.
Enter data in the Run Time Screen as shown below:
Now press
until the Alarm Summary Screen reappears on
the screen. Clear all of the alarms by pressing and holding
and then typing
. Wait for about 30 seconds, and the blank line
should disappear from the screen.
-----------------------------------------------------------------------------------------
Satellite # 1
TREND LOGGING # 1
of Type: RUN TIME
Records total ON time
Starting at: *:* on */*
for 1
logical on
Reset by: .... being OFF
Alarm
Type
8
Alarm
Message
#:
60
Current run time: -1 Hours
Alarm Limit: 9999 Hours
HOME for menu
-----------------------------------------------------------------------------------------