Section 3: Screen Descriptions

WCC II Operator’s Guide

Operator Interfaces

3-37

Clearing Random Data in Satellite
Run Time Registers

You may see some blank lines between two actual alarms on the
Alarm Summary Screen the fi rst time the ECC/WCC II system is
brought on line. These blank lines are caused by random data in
a satellite run time register the fi rst time a satellite controller is
powered up. If these registers are not cleared, the speed at which
the ECC/WCC II system can move from screen to screen will be
much slower.

To fi nd which satellite run time registers need to be reset, use the
arrow keys to move the cursor to one of the blank lines on the
Alarm Summary Screen and press

. The Run Time Screen

that needs to be reset will appear on the screen.

Enter data in the Run Time Screen as shown below:

Now press

until the Alarm Summary Screen reappears on

the screen. Clear all of the alarms by pressing and holding

and then typing

. Wait for about 30 seconds, and the blank line

should disappear from the screen.

-----------------------------------------------------------------------------------------

Satellite # 1

TREND LOGGING # 1

of Type: RUN TIME

Records total ON time

Starting at: *:* on */*

for 1

logical on

Reset by: .... being OFF

Alarm

Type

8

Alarm

Message

#:

60

Current run time: -1 Hours

Alarm Limit: 9999 Hours

HOME for menu

-----------------------------------------------------------------------------------------