Section 5: Installation Guide

WCC II Operator’s Guide

Operator Interfaces

5-37

Room Temperature Sensor

The WRS-1FVR fl ush mount or the TRS-VR wall thermostat may
be use with the TUC-VR. Both units require 4 wires from the sensor
to the TUC-VR. Use 18-22 gauge 4 conductor cable (stranded or
solid) for runs up to 100 feet. The wire should be twisted with a
minimum of 1½ turns per foot.

CAUTION:

Do not install the cable in the same conduit as

power wiring. If it is necessary to install the cable in areas of

high RFI/EMI, the cable must be installed in conduit. Do not

use shielded cable of any kind.

Isolation Transformer

Each TUC-VR must be powered by its own transformer. A
24V/24V isolation transformer is provided with each TUC-VR.

CAUTION:

Do not ground the secondary of the transformer.

Transformer frame must be grounded via ground wire or

conduit.

Aux, Max and Min Potentiometers

The TUC-VR also has 3 potentiometers labeled “AUX,” “MAX,”
AND “MIN.” The AUX potentiometer provides the “LOCAL SET
SETPOINT” for different items, depending on the position of the
function switches as shown below:

VAV Box

Aux Set Point

1. Cooling Only

MWU

2. Staged Reheat

Reheat

3. Time Prop. Reheat

Reheat

4. Prop Reheat Valve

Reheat

Parallel Fan Box

5. Cooling Only

Fan

6. Staged Reheat

Fan

7. Time Prop. Reheat

Fan

8. Prop. Reheat Valve

Fan

Series Fan Box

9. Cooling Only

Reheat

10. Staged Reheat

Reheat

11. Time Prop. Reheat

Reheat

12. Prop. Reheat Valve

Reheat

The MAX potentiometer is adjusted for the maximum air fl ow
allowed through the terminal unit. The MIN potentiometer is
adjusted for the minimum air fl ow allowed through the terminal
unit.