WattMaster WCC II User Manual
Page 65
Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-33
Starting at:
00:00 on 00/00
Specifi es the time and date that the trend log recording should
begin. (The time is represented in 24-hour format.) The system
considers *’s in these positions to be “wild cards.” Therefore, if
you want the system to log the run time independent of the time
and date, enter “*:* on */*.”
Reset by _______ being ____.
Specifi es the [binary] point address that will be used to reset (or
clear) the record trend log data. The fi rst fi eld specifi es the point
address, and the second specifi es the state or condition that the
point address needs to be in in order to clear the data.
Alarm Type: _____
Specifi es the priority (or “importance level”) for any alarms
generated by this input. Alarm types range from one (high priority)
to eight (low priority). The system responds to higher priority
alarms fi rst.
Alarm Message #: _____
Specifi es a message number for the run time alarm condition. This
number is used by the system to reference a textual message which
is displayed on the Trend Log Summary Screen.
Alarm Limit: ____ seconds
Specifi es a time limit at which point an alarm will be activated. That
is, when the total run time exceeds this limit, an alarm indication
will be sent from the satellite. The units of time will be the same as
that selected for the current run time.
Press
If you want to reset (clear) the existing trend log data, you may
do so by pressing and holding
and then typing
. After
several seconds this will automatically reset (clear) the data on the
Trend Log Screen (you must leave the screen and come back to it
for the screen to clear). On new systems, each Trend Log Screen
should be reset after it has been programmed to clear out any
“random data” that might be in the satellite controller.