Section 3: Screen Descriptions

WCC II Operator’s Guide

Operator Interfaces

3-146

ANALOG INPUT SCREEN

The term “analog” means a value that is represented by a directly
measurable quantity such as room temperature. “Input” means that
the analog value is sent to the ECC/WCC II system. Therefore, the
room temperature sensor is an analog input for the TUC-VR.

When SAT II controllers are used with the ECC/WCC II system,
each satellite can have 8 analog inputs which are referred to as
A1-A8. Since the SAT II-B is viewed as 4 SAT II controllers, the
TUC-VR room temperature sensors are seen as the analog inputs
of 4 SAT II controllers.

For example, if a SAT II-B is named #4, then it will appear as
satellite numbers 4, 5, 6, and 7 on the ECC/WCC II System Screens.
The following table shows how the TUC-VR’s will appear to
the ECC/WCC II system. For example, the room temperature
sensor connected to TUC-VR #20 will be seen at the ECC/WCC
II Operator Control Console as analog input 4 (A4) on satellite
controller #6.

Notes:

Analog

Input

SAT II-B #

A1

A2

A3

A4 A5

A6 A7

A8

4 (Base Number)

TUC1

TUC2

TUC3 TUC4

TUC5

TUC6

TUC7

TUC8

5 (Base Number+1)

TUC9

TUC10

TUC11 TUC12

TUC13

TUC14 TUC15

TUC16

6 (Base Number+2)

TUC17

TUC18

TUC19

TUC20

TUC21

TUC22 TUC23

TUC24

7 (Base Number+3)

TUC25

TUC26

TUC27 TUC28 TUC29 TUC30

TUC31 TUC32