Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-146
ANALOG INPUT SCREEN
The term “analog” means a value that is represented by a directly
measurable quantity such as room temperature. “Input” means that
the analog value is sent to the ECC/WCC II system. Therefore, the
room temperature sensor is an analog input for the TUC-VR.
When SAT II controllers are used with the ECC/WCC II system,
each satellite can have 8 analog inputs which are referred to as
A1-A8. Since the SAT II-B is viewed as 4 SAT II controllers, the
TUC-VR room temperature sensors are seen as the analog inputs
of 4 SAT II controllers.
For example, if a SAT II-B is named #4, then it will appear as
satellite numbers 4, 5, 6, and 7 on the ECC/WCC II System Screens.
The following table shows how the TUC-VR’s will appear to
the ECC/WCC II system. For example, the room temperature
sensor connected to TUC-VR #20 will be seen at the ECC/WCC
II Operator Control Console as analog input 4 (A4) on satellite
controller #6.
Notes:
Analog
Input
SAT II-B #
A1
A2
A3
A4 A5
A6 A7
A8
4 (Base Number)
TUC1
TUC2
TUC3 TUC4
TUC5
TUC6
TUC7
TUC8
5 (Base Number+1)
TUC9
TUC10
TUC11 TUC12
TUC13
TUC14 TUC15
TUC16
6 (Base Number+2)
TUC17
TUC18
TUC19
TUC20
TUC21
TUC22 TUC23
TUC24
7 (Base Number+3)
TUC25
TUC26
TUC27 TUC28 TUC29 TUC30
TUC31 TUC32