beautypg.com

Point addresses, Operator interfaces 1-7, Table of point addresses – WattMaster WCC II User Manual

Page 17: Constant point addresses

background image

Section 1: General Instructions

WCC II Operator’s Guide

Operator Interfaces

1-7

Point Addresses

A Point Address uniquely identifi es a point within the ECC/WCC
II system. All point addresses have an associated “analog” or
“binary” value. The term “analog” simply means a value which
is represented by a number (such as room temperature, duct static
pressure, etc.). The term “binary” means the value is represented by
one of two conditions, ON or OFF. An input is a signal sent to the
ECC/WCC II system, and an output is sent from the ECC/WCC II
system. Therefore, room temperature is an analog input, fan status
is a binary input, and controlling a fan relay is a binary output.

In addition to the inputs and outputs that are wired to the SAT
II controllers, there are several software point addresses within
the system. For example, the ECC/WCC II system has 32 week
schedules. This means that a separate day/night schedule can be
assigned to 32 different areas of the building.

For example, assume that you have three different areas in a
building that have different schedules as shown in the following
table.

Area

Occupied Time

Week Schedule #1

1st Floor West

8:00 am - 5:00 pm, M-F

Week Schedule #2

1st Floor East

7:00 am - 7:00 pm, M-F

Week Schedule #3

2nd Floor

9:00 am - 4:00 pm, M-Th

Week Schedule #1 is named W1, and the value of W1 will be On
between 8:00 am and 5:00 pm, Monday through Friday, etc.

The Name column in the table that follows is the name that you
should use when specifying a point address to the system. The “n”
is where a “point number” for the point address is to be entered.

Table of Point Addresses

Name

Description

Value

Cn

Comparator (See analog input

screen binary setpoint)

On/Off

An

Analog Inputs

Analog

Pn

Analog Inputs

Analog

KnH

Control Outputs

(H Contacts)

On/Off

KnC

Control Outputs

(C Contacts)

On/Off

RnA

Data Registers (a)

Analog

RnB

Data Registers (b)

Analog

TnR

Trend Logging Run Time

Analog

Name

Description

Value

TnC

Trend Logging Change of State

None

TnA

Trend Logging Analog Trend

None

TnP

Trend Logging Analog Peak

None

Ln

Logical Input

On/Off

Wn

Week Schedules

On/Off

Sn

Optimal Starts

On/Off

GBn

Binary Globals

On/Off

GAn

Analog Globals

Analog

Constant Point Addresses

The following list shows several point addresses within the
system that are always available for use on many of the data input
screens.

Name

Description

Associated Data Type

0

Logical Zero

Always Off

1

Logical One

Always On

////

Logical Null

Ignored

. . . .

Logical Off

Always Off/Not Used

Note:

When a point option is not required, replace the default

value (/ / / /) with either a zero (0) or dot (. . . .) to force the

system to realize that the option is always OFF. If the slashes

are not replaced, the system will ignore that input and the

system can, in rare cases, see the slashes as being ON.

Name

Description

Analog 0

Initiates a 0 (zero) value

TIME

Current Time (in HH:MM format)

TIMEB

Current Time (in minutes-since-midnight format)

NEWSEC

New Second

NEWMIN

New Minute

NEWHR

New Hour

NEWDAY

New Day

NEWMON

New Month