Binary global screen - combinatorial mode, Tenant override report – WattMaster WCC II User Manual
Page 150
Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-118
In the above example, assume that air handler #1 (AHU #1) is ON
whenever global binary GB1 is ON.
AHU #1 provides the cooling for the offi ces for the occupants
listed on Tenant Override Screens 1, 2, and 3. When the cooling
is overridden from a tenant listed on screen #1, GC1 will go ON,
causing GB1 to ON, which in turn causes AHU #1 to go on. When
the cooling category is requested from a tenant listed on screen 2,
GC2 goes ON, which will also cause AHU #1 to go ON.
Remaining Override Time
The amount of override time remaining will be displayed here in
an hour and minute format. When the override is not active, this
portion of the screen will be blank.
Alt-R for Report
The amount of time the tenants use the override is recorded by the
ECC/WCC II system and can be displayed by pressing
and
. The following screen will appear:
Binary Global Screen - Combinatorial Mode
-----------------------------------------------------------------------------------------
BINARY
Global
#:
1
name
is
GB
1
Description: AHU #1
On Message #: 1 ON
Mode: Combinatorial
Off Message #: 2 OFF
Value is ON when ANY of the following conditions are met.
W1 is ON default true
GC1 is ON default false
GC2 is ON default false
GC3 is ON default false
Local set this global defaults to ON
----------------------------ALARM------------------------------
Set Condition: None
Type: 0
Message 0
HOME for menu
-----------------------------------------------------------------------------------------
Tenant Override Report
-----------------------------------------------------------------------------------------
Tenant number: 001
Month: [Jul.]
Option: [Total]
Name Equipment Start
End
Elapsed Time Total
Bill
Light
8:00
Heat
0:00
A/C
6:00
-----------------------------------------------------------------------------------------