beautypg.com

Dark alarm – KEYENCE LT-9001 Series User Manual

Page 63

background image

3

Chapter

Operations

and

Fun

ction

Settings

in
the

Displacement

Mo

de

E LT-9001-IM

Displays and outputs the DARK ALARM when the

light intensity peaks are not measured within the

set range.

When every light intensity peak is under the lower

limit of the set range, the system goes into the DARK

ALARM status. It recovers when the light intensity

peak of one or more surfaces exceed the upper limit.

The procedure used to set the DARK ALARM is

explained as follows.

1

Select [DARK] from [BASIC] on the program

mode screen.

The dark status setting screen appears.

2

Select [DARKOUT].

3

Set [DARKOUT] to [ON] by using the [

] and

[

] buttons.

Set to [OFF] when you are not using this

function.

DARK ALARM

3-17

4

Place the cursor on [SETTING RANGE] and

select by pressing the [ENTER] button.

The range setting screen appears.

5

Select the cursor for either the upper or lower

limit by using the [SCREEN] button.

The selected cursor turns to yellow-green.

6

Set the position for the cursor of the upper or

lower limit by using the [t] or [s] button.

7

Press the [ENTER] button.

The dark setting is fixed.

Refer to "Default Values and Setting Range"

(page 2-25) for the setting range and limitations.

The dark status takes priority over any other

status. Refer to "Status Table" (page 9-4) for the

respective display/output statuses.

You can confirm the setting range with the dark

setting display bar while measuring.

You can confirm whether a target is within the

measurement range or not if DARK ALARM is set to

be displayed/output when the target is out of the

range and the light intensity become deficient.

Reference