beautypg.com

Auto-zero input program no. change input – KEYENCE LT-9001 Series User Manual

Page 120

background image

7-6

Identifying Names and Functions of the I/O Terminal

Auto-zero input

Program No. change input

The relationship between program numbers and terminals P1 to P3 is as follows:

Refer to "Program" (page 6-6) for details.

E LT-9001-IM

I/O

Terminal

7

Chapter

Name

Description

Reference page

P1 to P3 input

Changes the program No. by external commands.

Page 7-4

Program No.

P3

P2

P1

0

OFF

OFF

OFF

1

OFF

OFF

ON

2

OFF

ON

OFF

3

OFF

ON

ON

4

ON

OFF

OFF

5

ON

OFF

ON

6

ON

ON

OFF

7

ON

ON

ON

ON: Short circuited state with the COM2 terminal

OFF: Open state

When you change the program No. via an I/O terminal, [P-SELECT] at the environment settings
should be changed to [TERMINAL].

Name

Description

Reference page

ZERO input

Sets the current measured value to zero.

Page 7-3

* A common input for OUT1 and OUT2