Chapter 7 Parameter
266
[33] Default acceleration/deceleration mode (Parameter No.52)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
52 Default Acceleration/
Deceleration Mode
CTLF
-
0 to 2
0 (Trapezoid
When a target position is written to an unregistered position table, this value is automatically set
as the “Acceleration/deceleration mode” of the applicable position number.
Set Value
Description
0
Trapezoid
1
S-motion
2
Primary delay filter
[34] Default stop mode (Parameter No.53)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
53 Default Stop Mode
CTLF
-
0 to 3
0 (Not applicable)
This parameter defines the power-saving function.
[Refer to Chapter 5 Power-saving Function.]
[35] Current control width number (Parameter No.54)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
54 Current Control Width Number
CLPF
-
0 to 4
In accordance
with actuator
This parameter is for the manufacturer’s use only to determine the response capability of
thecurrent loop control. Therefore, do not change the settings in this parameter. If the
parameter ischanged carelessly, control safety may be adversely affected and a very
dangerous situationmay result.
[36] Position command primary filter time constant (Parameter No.55)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
55 Position Command Primary Filter
Time Constant
PLPF
msec
0.0 to 100.0
0.0
This is to be used when setting the value in “Acceleration/Deceleration Mode” box in the
position table to 2 “Primary Delay Filter”.
The primary delay filter is disabled if “0” is set.
The greater the setting value is, the longer the delay is and the slower the
acceleration/deceleration is. The impact at the acceleration and deceleration will be eased, but
the takt time will become longer.
Velocity
Time